Appendix
A.1 List of important alarms and faults
Number
Cause
F07840
The "Infeed operation" signal is not available, though
the enables for the drive have already been pending
for longer than the parameterized monitoring time
(p0857).
Infeed not in operation.
•
Interconnection of the binector input for the 'ready'
•
signal is incorrect or missing (p0864).
Infeed is currently identifying the network.
•
A08526
No cyclic connection to the control is available.
56
Remedy
Put infeed into operation.
•
Check the interconnection of the binector input for
•
the "infeed operation" signal (p0864).
Extend monitoring time (p0857).
•
Wait for completion of the infeed network identifi-
•
cation.
Establish a cyclic connection and activate the
•
control with cyclic operation.
Check the parameters "Name of Station" and "IP
•
of Station" (r61000, r61001) on PROFINET.
If a CBE20 is inserted and PROFIBUS is to com-
•
municate via process data interface 1, then pa-
rameterize with the STARTER commissioning tool
or directly via p8839.
Getting Started, 11/2017, 6SL3097-4AG00-0BP5
Getting Started with STARTER