Start-Up And Adjustment - Trane UX2B060AFV3VA Series Installer's Manual

Upflow/horizontal, gas-fired, direct vent, 2-stage condensing furnaces with variable speed inducer and whole house air cleaner
Table of Contents

Advertisement

TABLE 10
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
PART
SIZE
NUMBER
44
ORF00501
45
ORF00644
46
ORF00909
47
ORF00910
48
ORF01099
49
ORF00503
50
ORF00493
Turn the main Gas Valve toggle switch (See Figures 30
& 31) within the unit to the "OFF" position. Turn the ex-
ternal gas valve to "ON". Purge the air from the gas
lines. After purging, check all gas connections for leaks
with a soapy solution -- DO NOT CHECK WITH AN
OPEN FLAME. Allow 5 minutes for any gas that might
have escaped to dissipate.
LP Gas being heavier than air may require forced ventila-
tion. Turn the toggle switch on the Gas Valve in the unit
to the "ON" position.

START-UP AND ADJUSTMENT

PRELIMINARY INSPECTIONS
WARNING
!
Disconnect power to the unit before removing the
blower door. Allow a minimum of 15 seconds for IFC
power supply to discharge to 0 volts.
Failure to follow this warning could result in property
damage, personal injury or death.
With gas and electrical power "OFF"
1. Duct connections are properly sealed
2. Air cleaner and filters(if applicable) are in place
3. Venting is properly assembled
4. Blower door is in place
TABLE 11
Orifice
ALTITUDE ABOVE SEA LEVEL
Twist Drill
Size If
and Orifice Required At Other Elevations
Installed
At Sea
Level
2000 3000 4000 5000 6000 7000 8000 9000 10000
42
42
43
43
43
44
44
44
44
45
45
45
45
46
47
47
46
47
47
47
47
48
48
49
54
54
55
55
55
55
55
55
56
56
56
57
57
58
59
59
58
59
60
60
From National Fuel Gas Code - Table F-4
18-CD25D1-2
DRILL
PART
SIZE
NUMBER
54
ORF00555
55
ORF00693
56
ORF00907
57
ORF00908
58
ORF01338
59
ORF01339
43
44
44
45
46
45
45
46
47
47
46
47
47
48
48
47
48
48
49
49
48
48
49
49
50
49
49
50
50
51
55
55
55
56
56
56
56
56
56
56
57
57
58
59
59
60
60
61
62
63
61
62
62
63
63
Figure 33
Gas Valve On / Off
Toggle Switch
LIGHTING INSTRUCTIONS
DO NOT ATTEMPT TO MANUALLY LIGHT THE BURNER.
FAILURE TO FOLLOW THIS WARNING COULD RESULT
IN PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
If this is done during the cold weather months, provi-
sions must be taken to prevent freeze-up of all water
pipes and water receptacles.
47
48
50
50
51
52
56
57
60
63
64
Lighting instructions appear on each unit. Each installa-
tion must be checked out at the time of initial start up to
insure proper operation of all components. Check out
should include putting the unit through one complete
cycle as outlined below.
Installer's Guide
2nd Stage (HI) Manifold
Pressure Adjustment
1st Stage (LO)
Manifold Pressure
Adjustment
White-Rodgers 36G
WARNING
!
CAUTION
!
Figure 34
ROTATE THE FRONT
COVER AS SHOWN
INSERT THE TOP FLANGE
OF THE FRONT COVER
UNDER THE LIP INSIDE
THE BOX
ALL SIDE FLANGES MUST
BE OUTSIDE OF THE BOX
ROTATE THE FRONT
COVER INWARD MAKING
SURE THAT ALL SIDE
FLANGES ARE OUTSIDE
OF THE BOX.
35