CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
P296
(1)(2)
Nominal Voltage
nominal voltage of
6.4 - SERIAL COMMUNICATION PARAMETERS - P300 to P399
P308
(1)(2)
Soft-Starter Address
on the Serial
Communication
Network
P309
(1)(2)
Fieldbus
Communication
Board Enabling
P310
Profibus DP or DP-V1
Master Stop Detection
119
Range
Unit
Description / Notes
0 to 1
[ According to the
the Soft-Starter
SSW-06 ]
-
1 to 247
Defines the Soft-Starter SSW-06 address on the serial Modbus-RTU
[ 1 ]
communication network.
1
For more information, refer to the Serial Communication Manual
for the Soft-Starter SSW-06.
0 to 9
[ 0=Inactive ]
-
Enables and defines the protocol type of the Fieldbus Communica-
tion Board.
For more information, refer to the Fieldbus Communication Manual
for the Soft-Starter SSW-06.
0 to 1
[ 0=Inactive ]
1
It allows, through the bit 6 of the control word, detecting that the
master of the Profibus DP or DPV1 is stopped. Refer to the Fieldbus
communication manual for more details.
When it occurs it will indicate E29. In order to prevent the error, the
master must keep the bit 6 in 1.
ATTENTION!
Always program this parameter with a current that exactly
matches the current of the model of your Soft-Starter SSW-
06, described in the nameplate of the SSW-06. An error in
programming this parameter may damage your Soft-Starter
SSW-06.
P296
Voltage Range
0
1
Table 6.33 - Voltage range
ATTENTION!
Always program this parameter with a voltage that exactly
matches the voltage of the model of your Soft-Starter SSW-06.
P309
0
Inactive
1
Profibus-DP (1 Input and 1 Output)
2
Profibus-DP (4 Inputs and 4 Outputs)
3
Profibus-DP (7 Inputs and 7 Outputs)
4
DeviceNet (1 Input and 1 Output)
5
DeviceNet (4 Inputs and 4 Outputs)
6
DeviceNet (7 Inputs and 7 Outputs)
7
EtherNet (1 Input and 1 Output)
8
EtherNet (4 Input and 4 Output)
9
EtherNet (7 Input and 7 Output)
Table 6.34 - Fieldbus Communication Protocol Type
NOTE!
Without a Fieldbus Communication Board, this parameter
must remain at 0 (not used).
P310
Description
0
Inactive
1
Active
Table 6.35 - Selection of the Profibus DP master stop detection
220/575V
575/690V
Action