Digalox DPM72-AV Instruction manual (Rev-2018-09)
Package contents: Panel meter Digalox DPM72, 5 × jumpers, 1 × mounting bracket
1. Intended use
Indoor use non condensing, non corrosive.
Panel mounting.
Failure to comply with these instructions will void all guarantee and warranty.
2. Safety instructions
Note: The measurement inputs of the device can carry life-threatening
voltages!
When working on the device hazardous voltages must not be connected to
the device!
The device must not be used as the only protective device or protective
shutdown.
Read instruction manual carefully before operating the device!
The device is not intended to protect persons or facilities against harm. Specific
devices must be used to guarantee safety (protection relays, cut-off switches,
etc.).
When connecting switches to the terminals J1-J6, only switches must be used
whose isolation voltage is at least twice the maximum occurring measurement
voltage. For example, when measuring 250 V AC switches must be isolated for
at least 500 V.
Do not open the housing!
Do not use the instrument in the presence of explosive or flammable substances!
All cables carrying hazardous voltages must be secured with external separators.
----- 1 -----

Advertisement

loading

Summary of Contents for TDE Instruments DPM72-AV

  • Page 1 Digalox DPM72-AV Instruction manual (Rev-2018-09) Package contents: Panel meter Digalox DPM72, 5 × jumpers, 1 × mounting bracket 1. Intended use  Indoor use non condensing, non corrosive.  Panel mounting.  Failure to comply with these instructions will void all guarantee and warranty.
  • Page 2 3. Description The measurement modes volt AC/DC, ampere AC/DC, frequency and 5 A current transformer are supported. Scale endpoint of the indicator as well as scaling of the analogue signal and current transformer measurement can be adjusted freely via the DIP switch, alternatively the option for automatic adaption of the scale endpoint can be used.
  • Page 3 4. Electrical Connections The device may only be operated in one of the connection options shown below. Supply Voltage direct 10 - 24 V Fuse 250 mA high high max. 500 V − Digalox +/L -/N Supply Current direct Current and voltage direct high high high...
  • Page 4 5. Configuration The device can be configured via DIP switches and jumpers. Scaling In modes where a scaling is necessary to represent the correct measurement value (for example 5 A AC for current transformer) the upper scale value corresponds to the primary value of the current transformer.
  • Page 5 Configuration of the upper scale caption The upper scale caption is binary coded using DIP switches 1-9. Possible values are 1 to 500. Switch 1 corresponds to 256, switch 2 corresponds to 128, switch 3 corresponds to 64, etc., switch 9 corresponds to 1. For configuration, proceed as follows: 1.
  • Page 6: Measurement Display

    Table common switch combinations Value Combination Value Combination (DIP switch 1-9) (DIP switch 1-9) 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12...
  • Page 7 6. Other settings The following functions can be activated independently by short-circuiting connectors J1-J3 by jumper or switch during operation: J1: Graphical historic data display To activate the graphical historic data display connector J1 is shorted. The unit displays the stored values within the set time base as a graphical trend.
  • Page 8 9. Cleaning Observe the safety instructions before cleaning the instrument. Clean the instrument with a dry lint-free soft cloth. Do not use solvents. 10. Contact Information TDE Instruments GmbH, Gewerbestraße 8, D-71144 Steinenbronn Phone: +49 7157-20801 E-Mail: info@tde-instruments.de Internet: www.tde-instruments.de, www.digalox.com...