Chapter 3

Configuring the UPS for EBMs

Avaya 9130 EBM Site Preparation, Installation and Operator's Manual

Operation

This chapter contains information on how to configure the UPS for
Extended Battery Modules (EBMs) and other battery settings.
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
Press any button on the front panel display to activate the menu
options, then select SETTINGS, USER SETTINGS, and NUMBER OF
BATTERY STRINGS.
2.
Use the
or buttons to select the number of battery strings
according to your UPS configuration:
All UPS and EBM Cabinets
UPS only (internal batteries)
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
UPS + 4 EBMs
NOTE If 0 is selected, no batteries are connected and all battery-related
alarms are disabled.
NOTE The UPS contains one battery string; each EBM contains two battery
strings.
3.
Press the
button to save the setting.
ESC
4.
Press the
button until the start screen appears.
Number of Battery Strings
1 (default)
3
5
7
9
S
164201770 Rev 1
27