Avaya 9130 Extended Battery Module (EBM) Site Preparation, Installation and Operator’s Manual www.powerware.com/avaya...
Page 2
For proper disposal, contact your local recycling/reuse or hazardous waste center. Avaya and the Avaya logo are trademarks of Avaya Inc. and may be registered in certain jurisdictions. Eaton and Powerware are registered trademarks of Eaton Corporation or its subsidiaries and affiliates. Phillips is a registered trademark of Phillips Screw Company.
Chapter 1 Introduction The Extended Battery Module (EBM) can be added to the Avaya 9130 ® uninterruptible power system (UPS) to extend the available battery time (see Table 1). Up to four EBMs can be installed with the UPS. Table 1. Battery Runtimes (in Minutes) at 100% Load...
Never dispose of batteries in a fire. Batteries may explode when exposed to flame. If the UPS requires any type of transportation, disconnect the UPS internal batteries before transporting (refer to the UPS user’s guide). Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 7
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 8
Houd onbevoegden uit de buurt van de accu’s. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 9
Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 10
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 11
Vorsichtsmaßnahmen verfügt. Nicht autorisiertes Personal von Batterien fern halten. Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. Batterien niemals verbrennen, da sie explodieren können. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 12
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 13
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 14
Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local para maiores informações sobre os regulamentos de descarte de produtos. Nunca jogue as baterias no fogo, porque há risco de explosão. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 15
Необходимо соблюдать правила утилизации аккумуляторов. Обратитесь к местным нормативным актам за информацией о требованиях к утилизации. Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 16
Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes. Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 17
Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 18
INTRODUCTION Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
NOTE Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your Avaya service representative. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual...
NOTE Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time. Use the UPS user’s guide instead to install both the UPS and the EBM. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
INSTALLATION Installation The Avaya 9130 rackmount cabinet comes with all hardware required for installation in a standard EIA or JIS seismic rackmount configuration with square and round mounting holes. The rail assemblies adjust to mount in 48-cm (19-inch) racks with front to rear rail distances from 61 to 76 cm (24 to 30 inches) deep.
Figure 1. Do not tighten the screws. Adjust each rail size for the depth of your rack. Rear Rails × 8 Pan-Head Screws (6 places) Left Rail Right Rail Figure 1. Assembling the Rails Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 23
Align the mounting brackets with the screw holes on each side of × the EBM and secure with the supplied M4 8 flat-head screws (see Figure 3). Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 24
Repeat for any additional EBMs. M6 Cage Nuts (4 places) × 16 Pan-Head Screws (4 places) Figure 4. Securing the Front of the Cabinet Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Grasp the top and bottom of the cover and slide the cover to the right. NOTE A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 26
To remove the cover, remove and retain the two screws on the right side of the cover. Grasp the sides of the cover and slide the cover to the left and then away from the cabinet. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 27
If you are installing more than one EBM, for each additional EBM remove the EBM cable knockout on the top and bottom of the EBM front cover. See Figure 8 for the location of the EBM cable knockouts. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 28
Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable. 1000/1500 VA Models 3000 VA Models Figure 9. Typical EBM Installation Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 29
10. Ensure maximum battery runtime by configuring the UPS for the correct number of EBMs (see page 27). 11. Charge the EBM(s) for the times recommended in Table 4 on page 40. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 30
INSTALLATION Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
NOTE The UPS contains one battery string; each EBM contains two battery strings. Press the button to save the setting. Press the button until the start screen appears. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
To pass the battery test, the battery voltage must remain above the threshold value during discharge. If the battery voltage drops below the threshold, the UPS returns to Normal mode and the front panel displays “Battery Test Failed.” Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
“Automatic Start Delay” setting. You can also configure UPS restart to depend on the battery charge level, using the “Battery Charge % to Restart” setting. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 34
OPERATION Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
If you store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The internal batteries charge to 90% capacity in less than 3 hours. However, Avaya recommends that the batteries charge for 48 hours after long-term storage.
4) Wear rubber gloves and boots. When replacing batteries, replace with the same type and number of batteries or battery packs. Contact your Avaya service representative to order new batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Page 37
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. Disconnect charging source prior to connecting or disconnecting battery terminals. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Top EBM Cable Knockout EBM Cover Hook Bottom EBM Cable Knockout (underneath cover) Figure 10. Removing the EBM Front Cover Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 39
EBM. Repeat for any additional EBMs. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each cable. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds. The front panel displays “Battery test running” and the percentage of the test completed. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
Page 42
MAINTENANCE Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...
The troubleshooting chart covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with your UPS, call your Avaya service representative or the appropriate telephone number on the service label of your UPS.
Page 46
SERVICE AND SUPPORT Avaya 9130 EBM Site Preparation, Installation and Operator’s Manual 164201770 Rev 1...