Specifications; General; Environmental - Honeywell Touchpoint 1 Technical Manual

Single channel gas detector controller
Table of Contents

Advertisement

General

Wall mounted single channel control panel for the local annunciation of gas
hazards as detected by the Zareba range of Sensepoint gas detectors.
Use
Suitable for small scale, indoor installations requiring a self contained gas
detection and control system
User interface
Single Test/Accept/Reset push-button for normal operational use. Three
Operation
further hidden push buttons for configuration via intuitive menu system
Channel status including measuring range, units of measure, digital gas
Backlit
reading, bar graph displays 0-100% full scale, status indicators including
display
alarm set point, alarm activated, and power health
Other
Ultra-bright LEDs: alarm (red), power (green), fault (amber)
Indicators
Audible Alarm 85 dBA at 1 m / 90 dBA at 1 foot, user hush facility, re-activated on new event
Accessed via hinged front cover (latch to hold open as required). All cable/
conduit entry via pre-formed knockouts in gland plate at bottom of controller.
Terminations
Screw terminals suitable for use with 0.5 mm
wires. Crimped connection recommended. Take care not to over tighten screw
terminals. The recommended torque setting for the terminals is 12 lb in.

Environmental

IP Rating
Indoor use, IP44 in accordance with EN60529:1992
Weight
2.5 Kg / 5.5 lb (approx.)
Operating
-10°C to +40°C / 14°F to 104°F continuous (up to +50°C/122°F intermittent)
Temp Range
Operating
Humidity
10 to 90% RH (non condensing)
Range
Operating
Pressure
90-110 kPa
Range
Storage
-40
TP1MAN Issue 3 Apr 06 (MAN0630)

Specifications

o
o
o
C to +80
C / -40
F to +176
2
(20 AWG) to 2.5 mm
o
F, 20 to 80% RH (non condensing)
Specifications
2
(14 AWG)
52