User Settings; Gas Units And Range - Honeywell Touchpoint 1 Technical Manual

Single channel gas detector controller
Table of Contents

Advertisement

The controller is supplied pre-configured with factory defaults, see page 45.
These can be used if suitable, or customized by the user to suit site requirements.
This chapter explains how to:
set gas units and range, see page 38
set zero and span, see page 40
browse Touchpoint 1's event record, see page 41
set alarm levels and relay actions, see page 42
set the real-time clock, see page 44
set the power source, see page 45
Before performing any of the above actions refer to the procedures that explain how to use
menus, see page 32.
The following table provides a summary of the configuration options available.
For detailed step-by-step instructions for each menu see the subsequent sections.

Gas Units and Range

If the range is changed, the alarm set points also change.
This menu is the first one displayed when the menu system is accessed. It sets the units of gas
measurement and the range.
1
Press the Up and Down buttons simultaneously.
This accesses the menu system and displays the
2
Press OK.
The current units and range are displayed.
3
Press Up or Down to select a different unit of gas measurement.
See the subsequent table.
4
Press OK to accept the selected unit.
The display now shows the current range.
5
Press the Up or Down down buttons to select a different range.
Default units and ranges are shown in this table.
Unit
Range
Caution If the range is changed, the alarm level will also be changed.
Set desired alarm levels per page 42.
TP1MAN Issue 3 Apr 06 (MAN0630)

User Settings

WARNING
Verify desired alarm set points.
kppm
ppm
1.0 - 999.9
1.0 - 999.9 or
10 - 9999
menu icon, which flashes.
%LEL
%v/v
10 - 100
1.0 - 100
User Settings
38