Service; Parameters; System Parameters - Swegon CONDUCTOR W1 Technical Manual

Table of Contents

Advertisement

Service

This section is intended only for use by personnel who are specially trained
by Swegon.

Parameters

In order to control the functions in the CONDUCTOR W1/W3, there are
a number of parameters, which can be changed in order to optimize the
current installation. In the display of the room unit (thermostat) every
parameter is shown in accordance with the figure below.
Figur 1.
Pos 1. Minimal value.
Pos 2. Parameter number.
Pos 3. Factory-preset value
Pos 4. Maximum value.
Pos 5. Parameter text.

System parameters

System parameters are basic parameters which are common for several
applications.
2
P_xxx
xxxxxx
Min xx
1
5
Main image in the display of the room unit
Display image
P_101
Modbus Address
min
1
P_102
BMS Baudrate, 9.6 19.2 38.4
min
1
P_103
BMS Parity 0=Od. 1=Ev. 2=None
min
0
P_104
BMS Stop bits
min
1
P_105
Component type, 2=DC, 3=RC
min
2
3
xxxxxx
Max xx
4
set
2
ID
max 247
set
3
max 3
set
2
max 2
1
max 2
3
max 3
Service
Description
Indicates the ModBus address.
Indicates the transmission speed
for connecting up to a Building
Management System (BMS).
1 = 9.6
2 = 19.2
3 = 38.4
Parity setting for connection
to BMS.
0 = Uneven
1 = Even
2 = None
Number of stop bits for
connection to BMS.
1 = 1 bit
2 = 2 bits
Indicates the current type of
controller.
5 : 41