Service
Trouble shooting
An alarm is initiated when an error arises in the control system. There are
two types of alarms:
Trouble shooting of the control system should always begin with
investigating whether any alarm has been initiated and if so which.
Certain alarms are automatically reset (Auto) after the cause of the error has
been remedied, while other alarms have to be manually (Man) reset.
If the control system is connected to a ModBus system, the alarms can be
read within the 10100 – 10139 range.
5 : 50
General alarms.
Application alarms.
Alarm
Alarm text
No.
0.
No active alarms
1.
No room unit 1
2.
No room unit 2
3.
No pressure sensor
4.
No supply flow sensor
5.
No exhaust flow sensor
6.
Room unit 1
temperature
7.
Room unit 2
temperature
8.
Controller KTY short
circuit
9.
Controller KTY open
circuit
10.
Room unit low battery
11.
PT-controller overload
12.
Set point not reached
13.
TBD
14.
TBD
15.
No device list
16.
AC overload
17.
System fault
18.
No serial number
Description /
Remedial
Cause
measure
No active alarms present.
No measure required.
The controller has not
Make a new
received any signal from
connection – Radio
the room unit 1 within
Frequency mode.
the given time (P_110).
Check the cable.
The controller has not
Check the cable.
received any signal from
the room unit 2 within
the given time (P_110).
Pressure sensor is missing
Install or replace the
or is defectiveive. Alarm is
sensor.
initiated after given time
(P_113).
Flow sensor is missing or
Install or replace the
is defectiveive. Alarm is
sensor.
initiated after given time
(P_113).
Flow sensor is missing or
Install or replace the
is defectiveive. Alarm is
sensor.
initiated after given time
(P_113).
No temperature from
Change room unit!
room unit 1.
No temperature from
Change room unit!
room unit 2.
KTY sensor defectiveive.
Replace the KTY
sensor.
KTY sensor missing.
Check connection of
the KTY sensor.
The level on the battery in
Replace the batteries
the room unit is low.
in the room unit!
The output signal has
Check water the
been +100% or -100%
temperature and the
during given time
water flow.
(P_111).
Set temperature, set flow
Check the water
or pressure has not been
temperature, the
reached within given time
water flow and the
(P_112).
airflow.
-
-
-
-
-
-
The supply voltage is too
Check the voltage
high.
source.
Component error.
Replace the controller!
Program error.
Replace the controller!
Resetting
-
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
-
-
-
Auto
-
-