Product overview
2.2 Hardware properties
Properties
CPU 1518-4 PN/DP MFP has the following properties:
Property
CPU display
Supply voltage
PROFIBUS DP
PROFIBUS interface (X4)
Operation of the CPU as a
DP master
PROFINET IO
PROFINET interface (X1
P1 R and X1 P2 R)
PROFINET interface
(X2 P1)
PROFINET interface
(X3 P1)
Operation of the CPU as
IO controller
I-device
22
Description
All CPUs of the SIMATIC S7-1500 product series fea-
ture a display with plain text information. The display
provides information on order numbers, firmware ver-
sion and serial numbers of all connected modules. In
addition, you can set the IP address of the CPU and
make additional network settings. The display shows
error messages directly as plain text.
The 24 V DC supply voltage is fed via a 4-pin plug
located on the front of the CPU.
The interface is used for connecting to a PROFIBUS
network.
In the role as a DP master, the CPU responds to the
connected DP slaves. It is not possible for the CPU to
take the role of a DP slave.
The interface has two ports. In addition to basic
PROFINET functionality, it also supports PROFINET IO
RT (real time) and IRT (isochronous real time).
The interface has one port. In addition to basic
PROFINET functionality, it also supports PROFINET IO
RT (real time).
The interface is used to:
Link development tools for C/C++ applications
Connect the TIA portal to the development of
STEP 7 applications
Communicate to the "outside world" from C/C++
Runtime
Communicate internally between C/C++ and CPU
Runtime (via virtual network)
IO controller:
As an IO controller, the CPU addresses the con-
nected IO devices
I-device
As an I-device (intelligent IO device), the CPU is
assigned to a higher-level IO controller and is used
as an intelligent pre-processing unit for subroutines
Additional information
S7-1500, ET 200MP system
manual
(http://support.automation.sieme
ns.com/WW/view/en/59191792)
SIMATIC S7-1500 Display Simu-
lator
(http://www.automation.siemens.
com/salesmaterial-as/interactive-
manuals/getting-started_simatic-
s7-1500/disp_tool/start_en.html)
Section Connecting up (Page 36)
S7-1500, ET 200MP system
manual
(http://support.automation.sieme
ns.com/WW/view/en/59191792)
PROFIBUS function manual
(https://support.industry.siemens.co
m/cs/ww/en/view/59193579)
PROFINET function manual
(http://support.automation.siemens.c
om/WW/view/en/68039307)
S7-1500 ODK 1500S manual
(https://support.industry.siemens.co
m/cs/ww/en/view/109249838)
PROFINET function manual
(http://support.automation.siemens.c
om/WW/view/en/68039307)
CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0)
Manual, 12/2017, A5E40882737-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents