Download Print this page

Neptronic BM000 Specification And Installation Instructions page 3

Advertisement

PC Board
Potentiometer
1
2
3
4
Stroke Adjustment – No control signal change
1.
Apply power and, wait for at least 10 seconds.
2.
Press and release the reset button to start the auto-stroke process.
The LED should be illuminated.
a.
First option:
The actuator will then travel in both directions to find its limits and position itself according to the demand.
The LED will extinguish, the process is complete.
b.
Second option:
When the desired end position is reached, press and release the reset button. The actuator goes to the start
position. You can also press and release the reset button when it reaches the start position. Once this process is
complete, the LED extinguishes.
Programming – Change of control signal
a.
Remove power and put all dip switches to "OFF" (Default).
b.
Apply power and, within 10 seconds, press and release the reset button. The LED should be blinking.
c.
Select the control signal with DIP switches:
DIP Switch
Move DS #1 to ON and then OFF
Move DS #2 to ON and then OFF
Move DS #3 to ON and then OFF
d.
If PWM mode is selected; when programming is done
- If DIP switch #3 is ON, PWM uses 5-second pulse
- If DIP switch #3 is OFF, PWM uses 25-second pulse
Stroke adjustment
see the stroke adjustment section above.
www.neptronic.com
BM060
Terminal
LED
Reset
button
5
Dip switch
Signal
Digital, On/Off or 3 point floating
PWM
Analog (default)
Specification and Installation Instructions
DIP Switch Settings
Rotation: CW
Fail safe return at 0°
PWM mode: 25-sec pulse
Other modes: see note*
ON
NOTE*: To use DIP switch #3 in other modes
(analog/digital), refer to Feedback Selection (CCW
1 2 3
Direction) on page 4.
BM Series Actuators
Rotation: CCW
Fail safe return at 90°
PWM mode: 5-sec pulse
OFF
Other modes: see note*
ON
ON
1
2
3
1
2
3
ON
3

Advertisement

loading

This manual is also suitable for: