Programming
Relay Output Configuration
relay [1-5] func = [0-9] -- relay function; relay 5 is the pulse output
0: Totalizer
1: Alarm
2: Manual Control
relay [1-5] input = [0-8] -- relay input; depends on source for totalizer:
0: Flow 1 Total
1: Flow 2 Rate
2: Flow Sum Rate
3: Flow 1-2 Rate
Flow 2-1 Rate
for alarms:
0: Flow 1 Rate
1: Flow 2 Rate
2: Flow Sum Rate
3: Flow 1-2 Rate
4: Flow 2-1 Rate
relay [1-5] units = [0-19] -- units on setpoints/rates; depends on src/input
flow units: same as 'flow [1-2] rate units' above
volume units: same as 'flow [1-2] total units'
relay [1-5] manual = [on/off ] -- manually set relay on or off, if in manual mode
relay [1-5] rate = [x] -- totalizer rate
relay [1-5] ctime = [0-10000] -- pulse width in milliseconds
relay [1-4] latch = [on/off ] -- turn on/off relay latching
relay [1-4] setpoint = [x]
relay [1-4] setpoint = [x]
relay [1-4] relpoint = [x]
relay [1-4] setdelay = [x]
relay [1-4] reldelay = [x]
Analog Output Configuration
analogout [1-2] func = [0-3]
0: Flow rate
3: PID control
analogout [1-2] src = [0-4]
for flow rate:
0: Flow 1 rate
1: Flow 2 Rate
2: Flow sum
3: Flow 1-2
4: Flow 2-1
for PID control:
0: Flow 1 rate
1: Flow 2 rate
analogout [1-2] range = [0-1]
0: 0-20mA
1: 4-20mA
analogout [1-2] low = [x] -- value corresponding to 0 (or 4) mA
analogout [1-2] high = [x] -- value corresponding to 20mA
analogout [1-2] setpoint = [x] -- PID setpoint
analogout [1-2] P = [x] -- PID constants
analogout [1-2] I = [x] -- PID constants
analogout [1-2] D = [x] -- PID constants