Bacnet - Badger Meter Data Industrial 3100 Series User Manual

Industrial flow monitor
Table of Contents

Advertisement

BACnet

The Series 3100 flow monitor can be configured to communicate on a BACnet RS485 MSTP (Master Slave Token Passing)
system . Configuration is via the front panel keypad .
The following settings are required:
Baud Rate:
MSTP Address:
MSTP MAX master:
Device Instance:
Object Name
BACnet Address
BACnet BaudRate
Flow 1 Rate
Flow 2 Rate
Flow 1 Total
Flow 2 Total
Note 1: 0 = Auto, 1 = 9600, 2 = 19200, 3 = 38400, 4 = 76800
Note 2: The installer selects the units of measure from a list of pre-programmed units or creates custom units . BACnet
transmits in the same units as displayed on the front panel .
USB Communication
The Series 3100 flow monitor is ordered with an analog output option card . A five-pin USB connector is also included . As
much as possible, the commands mimic the use of the front panel controls .
To use this feature, the following are required:
PC with USB ports and Windows HyperTerminal or other communications software
FTDI Virtual COM port drivers http://www .ftdichip .com/FTDrivers .htm
USB 2 .0 A to Mini-B 5-pin cable
To communicate using HyperTerminal:
1 . Make sure that the monitor has a Mini-B five-pin connector on the back panel . The Series 3100 must have an analog
output option card installed and be marked Series # 3100-1x .
2 . Verify that the appropriate FTDI Virtual COM port drivers are installed on your computer .
3 . Plug the USB 2 .0 A end of the cable into a USB port on your computer . Plug the Mini-B five-pin end into the back of
the monitor .
October 2017
[9600, 19200, 38400 or 76800] . The recommended factory default is 9600 .
[0...127] . Each device must have a unique address .
[0...127] . This range must be greater than the highest address on the network .
[00000000...99999999] . This is a unique identifier for each device in the system .
I/O (Write/Read)
I/O
I/O
O
O
O
O
4. Run Hyper-Terminal ( From the Windows Start Menu) and create a new connection
name and ICON.
5. Configure this Port with 38400 baud, 8 data bits, 1 stop bit, no parity, and no flow co
When connected a "> " symbol will appear in the upper left corner of the main
6.
HyperTerminal display screen.
Figure 2: Hyper terminal connection screens
Press the "Enter Key". Both the Rx and Tx LED's on the front of the Series 3000 sh
7.
flash once, and
the "Badger Meter DIC ... Software Version..." text message should appear.
The Series 3000 is now communicating ready to take commands from the list below
Object Type
Object ID
Analog Value
Multi-State
Analog Input
Analog Input
Analog Input
Analog Input
CTL-UM-01026-EN-05
Units
AV1
See Note 1
MSV1
AI1
Same as Displayed
AI2
Same as Displayed
AI3
Same as Displayed
AI4
Same as Displayed
Programming
Page 25