4.3.5.1.

External Alarms

The external alarms are used to monitor the status of one or more external devices via
the Node AM. A UPS or entry alarm is among the items that might be connected to the
contact relay and monitored via the Node AM4. The cage clamp connectors are located
on the UI1-board.
Observe that the cross-sectional area of the wires to be connected must be in the range
from 0.4 - 0.8 mm
2
(AWG 26-20). Do not use wire-end sleeves.
All external alarms are defaulted to high (3.3V TTL) without connection. This setting may
be changed on the external alarm page to active high or active low. The severity levels of
the external alarms may be set via the web page. More information about the external
alarm settings is available in the web page and online help.
External Alarms 1 to 5
Input voltage range
Recommended input line
Nominal sink current to ground
Active level
Connectors
Page 42
MF0121ACP_uc.docx
4. Functional Description
USB connector
0 to 5 Vdc
Potential free
15 mA
High or low set via software
Cage clamps