SUBMERSIBLE ELECTRIC PUMP INSTALLATION
DIAGRAM
7
2
6
5
2
4
2
3
2
1
TECHNICAL APPENDIX
12
10
8
4
9
14
COMPONENTS REQUIRED FOR
CORRECT INSTALLATION
13
Control panel equipped with a main switch and thermal
•
relay for overload protection.
Non-return valve at 10 meters' distance from the delivery
•
ports, plus an additional non-return valve every 30÷50
meters of piping.
Gauge and gate valve at well mouth.
•
Electronic probes or floats for protection against dry
•
running.
Secure the drop cable to the pipe every 2÷3 meters of
•
piping.
Make sure the electric pump is installed at a safe
•
distance from the bottom of the well.
Make sure there is a minimum distance of 3 mm
•
between the diameter of the pump and the internal
diameter of the well.
During operation, make sure that the water circulation
•
speed around the motor is at least 8 cm/sec.
Make sure that the minimum dynamic level of the water
•
in the well is at least 1 m above the pump's delivery port.
1 - Submersible electric pump.
2 - Cable clamp.
3 - Level sensors for protection
against dry running.
4 - Non-return valve.
5 - Support bracket.
6 - Delivery pipe.
7 - Electrical cable for
motor power.
8 - Electric pump bleed/
priming cap.
9 - Pressure gauge.
10 - Diaphragm tank.
11 - Gate valve.
12 - Control panel.
11
13 - PTC/PT100 cable.
14 - Pressure transducer.
A - Distance between the clamps
that secure the drop cable
to the delivery pipe.
B - Distance from the bottom of
the well to the electric pump.
14