Download Print this page
Neptronic BM000S Specification & Installation Instructions

Neptronic BM000S Specification & Installation Instructions

Advertisement

Quick Links

Technical Data
Fail safe - Enerdrive
Power consumption
Power supply 22 to 26 VAC or 28 to 32 VDC
Approvals
Auxiliary switches
Ingress protection
Torque
Running time through 90º
Electrical connection
Inlet bushing
Control signal
Angle of rotation
Direction of rotation
Ambient temperature
Storage temperature
Relative Humidity
Weight
Dimensions
D
C
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System U.S.A. Patent #5,278,454
BMS/070620
Feature:
BM000S
BM060S
BBMS2000
BBMS2060
No
Yes
20 VA Peak,
6 VA
6 VA
No
IP22 equivalent to Nema type 2,
IP54 equivalent to Nema type 3R if water tight inlet bushings
(not supplied NEP617) are installed
0 to 90 degrees, mechanically adjustable (factory set with 90º stroke)
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Warning: Do not press the clutch when actuator is powered
A
B
Specification & Installation instructions
Mounts easy on round
& square shaft (with option –8).
External clutch for manual
adjustments.
Maintenance free.
Position indicator.
Fail safe by Enerdrive System
(on model 60 & 80).
Auxiliary switches
(on model 20 & 80).
BM800S
BM860S
BBMS2800
BBMS2860
No
Yes
20 Watts Peak,
6 Watts
6 Watts
40 to 56 VDC
22 to 26 VAC or 28 to 32 VDC
50 in.lb. [5,6 Nm] at rated voltage
90 - 110 sec (Fail-safe20-30 sec)
18 AWG [0.8 mm
2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
2 to 10 VDC or 4 to 20 mA (factory set 2 to 10 VDC)
-22ºF to +122ºF [-30º C to +50º C]
-22ºF to +122ºF [-30º C to +50º C]
5 to 95 % non condensing.
3 lbs. [1.4 kg]
Dimension
D
Old Number
BBMS2000
BBMS2021
BBMS2060
BBMS2080
BBMS2800
BBMS2821
1
BBMS2860
BBMS2880
BM020S
BM080S
BBMS2021
BBMS2080
No
Yes
20 VA Peak,
6 VA
6 VA
Yes
IP22 equivalent to Nema type 2
2
] minimum
Inches
A
1.50
3.26
B
C
6.60
model 00 & 60
3.01
model 20 & 80
3.72
Actuator
BM000S
BM020S
BM060S
BM080S
BM800S
BM820S
BM860S
BM880S
BM820S
BM880S
BBMS2821
BBMS2880
No
Yes
20 Watts Peak,
6 Watts
6 Watts
40 to 56 VDC
Metric (mm)
38.1
82.8
167.5
76.4
94.5
1

Advertisement

loading

Summary of Contents for Neptronic BM000S

  • Page 1 94.5 Caution We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
  • Page 2 BM000S/020S/060S/080S BM800S/820S/860S/880S Specification & Installation instruction Mechanical installation Manually close the damper blades and positioned the actuator at 0º or 90º. Slide the actuator onto the shaft. Tighten the nuts on the “U” bolt to the shaft with a 8mm wrench to a torque of 60 in.lb.

This manual is also suitable for:

Bm800sBm020sBm860sBm060sBm080sBm820s ... Show all