0313279_TWISTER II_UKUK_V1.1, 18-02-2019
7.
Use the pressure gauge to read the supply pressure and compare it with the value
from the appendix Gas details (see 13.3).
Note
Consult the mains gas supply company if the supply pressure is not correct. Take the
water heater out of service until the supply pressure is correct, refer to section
Decommissioning (see 8.10).
8.
Set the control switch on the front of the water heater to 0 to turn off the water
heater.
9.
Shut off the gas supply.
10.
Disconnect the pressure gauge.
11.
Tighten the sealing screw in the test nipple.
Fig. Gas supply pressure
1
4
CO
value
2
Check the CO
value:
2
1.
Open the gas supply.
2.
Remove the cap (1) from the test nipple (2) of the flue gas outlet pipe.
3.
Place the measurement probe of the CO
outlet pipe.
4.
Turn on the water heater (see 4.1).
5.
If necessary, create a heat demand:
-
Use a hot water draw-off point to tap water, or
-
Raise the setpoint of the water temperature, refer to Set the water
temperature.
6.
Wait until the measured value on the CO
can take several minutes.
7.
Compare the full load measured value to the value from the appendix Gas details
(see 13.3).
The CO
value at full load must be within ±1.0 vol% of the CO
2
table.
3
2
meter in the test nipple of the flue gas
2
meter remains stable for some time. This
2
1. Adjuster screw
2. Sealing screw
3. Gas control valve
4. Gas supply pipe
value stated in the
2
51