3.2. Network Baudrate (f831)

Set the network baud rate to f831. Set the same baud rate data in the network.

3.3. Network error detection (f832,f851,f852)

Set the network communication loss action time to f832. The network loss action
function starts from receiving the properly frame message. The action of the network
communication loss is set by f851.
When setting of f851 is set other than 4 when it was detected, `t' alarm occurs with the
inverter.
In addition, in the case of f851= 5, it runs at designated frequency in "Preset speed
operation selection(f852)".

3.4. Reset to factory defaults (f833)

This parameter(f833) is connected to point number one hundred(Pno.100).
Reset is possible to factory setting in offline by using this parameter.
Point number one hundred is called the factory flag.
factory flag is used to determine if the initial values need to be "initialized." If the factory
flag does not equal ACH, the initial value for each subpoint will be set equal to the default
value. Then, the factory flag is set to ACH,

3.5. Station address (f834)

This parameter is connected to Pno.1.
Address setting is possible in the offline state which is not connected to the network.
The station address can be set between 1 and 99
When it was set to out of range, APG001Z converts it into 99, and the value of Pno.1 and
F834 becomes 99.
The station address must be unique and not match any other device on the network.