Vf-Ps1 Parameters; Communication Parameters - Toshiba APOGEE FLN APG001Z Function Manual

Option unit for tosvert vf-ps1 series inverter
Hide thumbs Also See for APOGEE FLN APG001Z:
Table of Contents

Advertisement

3. VF-PS1 Parameters

3.1. Communication parameters

Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not set
to correct value, this unit can not work normally.
Commu
Title
nication
No.
0831
Network Baudrate (*1)
f831
0832
Network Time-Out (*1)
f832
f833
0833
Factory setting (*1)
0834
Station address
f834
Operation
0851
at communication error
f851
by disconnection
Preset speed operation
0852
f852
selection
Communication
0853
station address monitor
f853
(Read Only)
Network
0899
f899
setting
Add-on
FE66
version(Under side option)
Add-on
FE67
version(Panel side)
* When fmod or cmod is set to "Communication option input", VF-PS1 drives without
FLN LOC REF (LDO point #69) or FLN LOC CTL (LDO point #68) at each Objects.
(*1): This parameter is effective by reset. Please reset (power supply reset or f899=1)
after changing a set point.
Function
0: 9600bps,1: 4800bps,2: 9600bps
3: 19200bps,4: 38400bps,
5: 57600bps,6: 76800bps
Over 7 is 9600bps.
0: No action
Unit 0.1 sec, Setting range: 1 – 1000
Over 1000 is 100.0s.
Except ACh:Reset to factory setting
ACh:Finished with reset to factory setting
1-99
The range outside is converted into 99
0: Inverter stop, communication command,
frequency mode open (by cmod, fmod)
1: None (continued operation)
2: Deceleration stop
3: Coast stop
4: Network error (err8 trip)
5: Preset speed operation (by f852 setting)
0:None
1~15:Preset speed operation (by parameter
option
Real station address monitor
If a value of f834 is out of a range, the value
of f853 becomes 99.
option
reset
0:None
1:Reset option circuit board and inverter
High byte is version. Low byte is revision.
For example, When version number 1, and
revision
option
1
CPU
becomes with 1.02.
The version of the option with it has equipped
can be checked by using the function of
f710 to f718 (standard monitor display
selection).
option
2
CPU
*For details, refer to the inverter instruction
manual.
- 5 -
Description
setting)
number
2
is,
E6581542①
Factory
setting
0000
0000
0000
(ACh)
0000
0
0
panel
indication
0