Ldo Point Descriptions - Toshiba APOGEE FLN APG001Z Function Manual

Option unit for tosvert vf-ps1 series inverter
Hide thumbs Also See for APOGEE FLN APG001Z:
Table of Contents

Advertisement

4.4.1.

LDO Point Descriptions

Table 9
Point
Point
Number
Name
22
CMD FWD.REV
24
CMD STP.STRT
26
EXT1.2 CMD
29
DAY.NIGHT
40
DO 1 COMMAND
41
DO 2 COMMAND
42
DO 3 COMMAND
43
DO 4 COMMAND
44
DO 5 COMMAND
45
DO 6 COMMAND
48
RST RUN TIME
49
RESET KWH
59
LOCK PANEL
68
FLN LOC CTL
Logical Digital Output (LDO)
Commanded from the FLN network to change the rotational direction of the
drive. This command is active only if the drive is configured for control from
the FLN network.
Commanded from the FLN network to start the drive. This command is active
only if the drive is configured for control from the FLN network.
When an inverter is a trip, a stop (=0) is set automatically.
Commanded from the FLN network to select channel 1 or channel 2 as the
active control source (0 = #60 INPUT REF1, 1 = #61 INPUT REF2).
1 of the 5 mandatory FLN points required for compatibility with Siemens
control systems. It has no functionality in the drive application.
The data of this point is outputted to the terminal which chose the designated
data output 1 (Output-terminal selection number: 92(93)).
For example,when you control the output of an OUT1 terminal , please set
parameter f130 (OUT1 terminal) =
The data of this point is outputted to the terminal which chose the designated
data output 2 (Output-terminal selection number: 94(95)).
For example,when you control the output of an
parameter f131 (
OUT2
The data of this point is outputted to the terminal which chose the designated
data output 3 (Output-terminal selection number: 96(97)).
For example,when you control the output of an
parameter f132 (
terminal) =
FL
The data of this point is outputted to the terminal which chose the designated
data output 4 (Output-terminal selection number: 98(99)).
For example,when you control the output of an OUT3 terminal, please set
parameter f133 (OUT3 terminal) =
The data of this point is outputted to the terminal which chose the designated
data output 5 (Output-terminal selection number: 100(101)).
For example,when you control the output of an OUT4 terminal, please set
parameter f134 (OUT4 terminal) =
The data of this point is outputted to the terminal which chose the designated
data output 6 (Output-terminal selection number: 102(103)).
For example,when you control the output of an R1 terminal, please set
parameter f135 (R1 terminal) = 10
Reserved (does not work).
Commanded by the FLN network to reset the cumulative kilowatt-hour and
megawatt-hours counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the command is issued,
this point automatically returns to its inactive state. This "momentary"
operation avoids any need for an explicit command to clear the point before a
subsequent reset can be issued.
Command from the FLN network to lock the panel and prevent parameter
changes (1 = LOCK, 0 = UNLOCK).
Commanded from the FLN network to temporarily "steal" start/stop control of
the drive from its normal source and place it under FLN network control.
This functionality is analogous to placing the drive in HAND mode at the
panel, with the control being taken by the FLN network instead. HAND mode
at the panel has priority over this point. Thus, this point is only effective in
temporarily taking control from the digital inputs or some other internal control
functionality.
- 16 -
Point Descriptions
Parameter
92 (93).
OUT2
94 (95).
terminal) =
FL
96 (97).
98 (99).
100 (101).
2 (103).
E6581542①
terminal, please set
the
terminal, please set
the
the
the
the
the