4.2.1.

LAO Point Descriptions

Table 5
Point
Point
Number
Name
01
CTLR ADDRESS
02
APPLICATION
20
OVRD TIME
30
CURRENT LIM
31
ACCEL TIME 1
32
DECEL TIME 1
46
AO 1 COMMAND
47
AO 2 COMMAND
50
PRC PID GAIN
51
PRC PID ITIM
52
PRC PID DTIM
53
(PRC PID DFIL)
60
INPUT REF1
61
INPUT REF2
66
SPD OUT MIN
67
SPD OUT MAX
95
MBOX PARAM
96
MBOX DATA
99
ERROR STATUS
*1: When this point was changed, a parameter of the inverter related to this point is changed.
Logical Analog Output (LAO)
The FLN address of the drive. It can be set from the FLN network and by
the panel. *1:f834
The Application ID for APG001Z.
1 of the 5 mandatory FLN points required for compatibility with Siemens
control systems. It has no functionality in the drive application.
Sets the output current limit of the drive. *1:f601
Sets the acceleration time for ramp 1. *1:acc
(Note1)
Sets the deceleration time for ramp 1. *1:dec
(Note1)
Controls analog output 1(FM).
The FM analog terminal on each inverter can be directly controlled with the
computer. To use this function, set the FM terminal meter selection
parameter (fmsl) to 31 (communication data output).
This makes it possible to send out the data specified as FM analog output
data (AO 1 COMMAND) through the FM analog output terminal. Data can be
adjusted in a range of 0 to 2047 (resolution of 11 bits).
For details, refer to "Meter setting and adjustment" of the instruction manual
included with the inverter.
Controls analog output 2(AM).
The AM analog terminal on each inverter can be directly controlled with the
computer. To use this function, set the AM terminal meter selection
parameter (amsl) to 31 (communication data output).
This makes it possible to send out the data specified as AM analog output
data (AO 2 COMMAND) through the AM analog output terminal. Data can be
adjusted in a range of 0 to 2047 (resolution of 11 bits).
For details, refer to "Meter setting and adjustment" of the instruction manual
included with the inverter.
Sets the proportional gain of the
PID. *1:f362
Sets the integration time of the
PID. *1:f363
Sets the derivation time of the
PID. *1:f366
Reserved (does not work).
Sets setpoint 1. This setpoint is enabled at #26 EXT1.2 CMD = 0.
For being available, some parameter(s) of the drive command require(s) a
specific configuration (setpoint channel 1).
Sets setpoint 2. This setpoint is enabled at #26 EXT1.2 CMD = 1.
For being available, some parameter(s) of the drive command require(s) a
specific configuration (setpoint channel 2).
Sets the minimum output speed of the drive as a percentage of the motor
nominal rating. *1:ll
Sets the maximum output speed of the drive as a percentage of the motor
nominal rating. *1:ul
Sets the parameter to be used by the mailbox function. Refer to section 5.
Sets or indicates the data value of the mailbox function. Refer to section 5.
1 of the 5 mandatory FLN points required for compatibility with Siemens
control systems. It has no functionality in the drive application.
Point Descriptions
Description
=
y
Pno
- 12 -
E6581542①
Δ
.
50
x
1
t
+
Δ
+
xdt
Pno
.
52
Pno
.
51
0
Δ
d
x
dt