8. Adding or replacing electronic ballasts

For cases where individual DALI electronic ballasts are to be
replaced, or others added, there is a DALI maintenance mode. In
DALI maintenance mode, only DALI electronic ballasts with a
short address of "FF" have their addresses reset and released for
grouping. This short address is saved as a factory setting on all
new DALI electronic ballasts.
50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818

9. Set Lux setpoint

9.1. Alignment

Always align the light sensor towards a lighting area belonging to
Group 1. For this, the sensor can be angled vertically at 30° from
the floor towards the wall.

9.2. Default settings

To adjust a desired target value more easily, it is recommended
to pre-set a value using the app and the parameter LUX or via
potentiometer which serves as basis for adjusting the desired
target value.

9.3. Process description

Step 1: Darken the room. There should be only light
available, which can be implemented via the device
connected to the detector lighting system.
Step 2: Place a calibrated light meter in the field of
group 1
Step 3: Use the manual dimming and eyes button in
the smartphone app in the tab „command", to store
the desired setpoint LUX. It may take up to 2 minutes,
until the new adjustment shows effect.
Step 4: Use the + / - buttons in the smartphone app
for minimal corrections