PD4-M-HCL 93006/93007

1.7. IR-Adapter

Lighting zones can only be parameterised sending infrared
signals via Smartphone app. Factory setting of the detector is
broadcast mode (white LED shines permanently). So it is possible
to check all DALI bus connections and pushbutton connections
without parameterising. To send infrared signals via the
Smartphone or a tablet, an IR-Adapter (part no. 92726) is
required, which must be charged periodically, and has to be
plugged in to the audio socket of the Smartphone or tablet.

2. Commissioning without IR-Adapter

2.1. Self-test cycle

In the first 60 seconds from when the mains voltage is turned on,
the detector runs through a self-test cycle. During this period, the
device does not react to movement.

2.2. Factory settings

The PD4-M-HCL can also be put into service with basic
functionality without changing any settings. Out of the box, the
detector works in Broadcast mode (white LED shines
permanently), which can only be changed over to Group mode
with the remote control (smartphone or tablet + IR-Adapter +
app) and the command "UNLOCK". All push buttons are activated
in Broadcast mode (switching and dimming).

2.3. Potentiometer and DIP switches

The following settings can be made via potentiometer and DIP
switches:
Cut-off (CO): Standby consumption of
connected DALI electronic ballasts is
automatically minimised / HVAC
(5,10,15): light-independent HVAC
occupancy control / HVAC (30,40,50,
60,120):
occupancy control with 5 min. switch-
on delay / OFF: No relay control
Moon:
Night mode (< 10 lux) / Set value in
lux:
900 /
Sun:
Day
mode
regulation, "too dark" detection
always active)
50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818
light-independent
HVAC
100,150,200,300,400,500,700,
(no
constant
light
Test: Each movement, regardless of
ambient light levels, switches the light
on for 1 second, then off for 2 seconds
(PLEASE NOTE: Test mode is only
possible if potentiometer B is not in
the "Sun" position) / Follow-up time
for
lighting
1,5,10,15,20,25,30,60
Nr.
Parameter/
Description
Function
DIP 1.
Soft Start
ON: initially to 10% at switch-on, then rising
to set value / OFF: initially to 100% at
switch-on, then falling to set value
DIP 2.
Init-Light
ON: when voltage is applied to detector, all
lights turn on at 100% /
OFF: when voltage is applied to detector, all
lights are off (0%)
DIP 3.
Auto-ON
ON: full automatic broadcast or
lighting zone A / OFF:
semi-automatic broadcast or lighting zone A

2.4. Factory Reset

Factory settings inclusive Broadcast-modes can be restored at
any time in the following manner (warning - all previous settings
will be lost):
Turn on mains supply if not already on
Turn "TIME" potentiometer to "Test" (if the potentiometer
is already in the "Test" position, it must first be turned to
another position)
Turn "LUX" potentiometer to "Sun" (if the potentiometer is
already in the "Sun" position, it must first be turned to
another position)
When all LEDs blink for approx. 3 seconds, activation of factory
settings inclusive Broadcast-Modus has been successfully
completed.