Advertisement

Quick Links

PD4-M-HCL 93006/93007
Application description
(to be translated: 08/08/2018)
50570_V1_Operation_Manual_PD4-M-
HCL_93006_93007_EN_080818
Content
1. Operation .......................................................................... 2
1.1. General .......................................................................... 2
1.2. Human Centric Lighting ................................................. 2
1.2.1. HCL Mode .............................................................. 2
1.2.2. Application profiles ............................................... 2
1.2.3. Date ....................................................................... 2
1.2.4. Time ...................................................................... 2
1.3. Groups and lighting zones ............................................. 2
1.3.1. Lightning zone A (main lightning) .......................... 3
lightning) ......................................................................... 3
1.4. Integrated relay with operating modes ......................... 3
1.5. Full automatic / semi-automatic mode .......................... 3
1.6. Push button functions.................................................... 3
1.7. IR-Adapter ..................................................................... 4
2. Commissioning without IR-Adapter .................................... 4
2.1. Self-test cycle ................................................................. 4
2.2. Factory settings ............................................................. 4
2.3. Potentiometer and DIP switches ................................... 4
2.4. Factory Reset ................................................................. 4
3. LED Indication .................................................................... 5
4. Bidirectional Smartphone App ........................................... 5
4.2. Preparing IR-Adapter ..................................................... 5
4.3. Connect Adapter with smartphone ............................... 5
5. Smartphone App Parameters ............................................. 5
5.1. General .......................................................................... 5
5.2. Device ............................................................................ 5
5.3. Human Centric Lighting ................................................. 6
5.4. Lighting .......................................................................... 6
5.5. DALI groups 1-3: lighting zone A .................................... 6
5.6. DALI groups 4: lighting zone B ....................................... 7
5.7. Orientation Light ............................................................ 7
5.8. Relay .............................................................................. 7
6. Smartphone App Commands .............................................. 7
6.1. DALI ............................................................................... 7
6.2. DALI group assignment .................................................. 7
6.3. Device ............................................................................ 8
7. Addressing and formation of groups................................... 8
7.1. Step 1: Broadcast Reset ................................................. 8
7.2. Step 2: New addressing process .................................... 9
8. Adding or replacing electronic ballasts ............................. 10
9. Set Lux setpoint ............................................................... 10
9.1. Alignment .................................................................... 10
9.2. Default settings ............................................................ 10
9.3. Process description ...................................................... 10
10. Article ............................................................................ 10
Page 1 / 10

Advertisement

Table of Contents
loading

Summary of Contents for B.E.G. LUXOMAT PD4-M-HCL-FC

  • Page 1: Table Of Contents

    PD4-M-HCL 93006/93007 Content Application description 1. Operation ................2 (to be translated: 08/08/2018) 1.1. General ................2 1.2. Human Centric Lighting ..........2 1.2.1. HCL Mode .............. 2 1.2.2. Application profiles ..........2 1.2.3. Date ............... 2 1.2.4. Time ..............2 1.3.
  • Page 2: Operation

    PD4-M-HCL 93006/93007 • In the "School" profile, the daytime brightness is controlled from approx. 350 to 500 lux and the colour temperature 1. Operation from approx. 3500 to 5500 Kelvin. 1.1. General 1.2.3. Date The PD4-M-HCL is a highly sensitive ceiling-mounted occupancy The current date must be transferred from the smartphone to detector based on passive infrared motion detection, with the detector via the app.
  • Page 3: Lightning Zone A (Main Lightning)

    PD4-M-HCL 93006/93007 1.3.1. Lightning zone A (main lightning) The PD4-M-HCL allows you to compensate for differences in brightness due to daylight coming from one side of a room fully automatically, using segmented constant light regulation in lighting zone A across 3 groups. Fittings with DALI electronic ballasts are thus grouped as follows: •...
  • Page 4: Ir-Adapter

    PD4-M-HCL 93006/93007 Test: Each movement, regardless of 1.7. IR-Adapter ambient light levels, switches the light on for 1 second, then off for 2 seconds Lighting zones can only be parameterised sending infrared (PLEASE NOTE: Test mode is only signals via Smartphone app. Factory setting of the detector is possible if potentiometer B is not in broadcast mode (white LED shines permanently).
  • Page 5: Led Indication

    PD4-M-HCL 93006/93007 4.3. Connect Adapter with smartphone 3. LED Indication Plug the adapter in to the audio socket of your Smartphone or tablet. You must ensure that the IR-Adapter is fully inserted into the socket. Nr. Indication white green Please note that covers or cases may partially block a correct Self-test cycle Blinking Blinking...
  • Page 6: Human Centric Lighting

    PD4-M-HCL 93006/93007 Status LEDs Date The status LEDs indicate – for example - Current date in the device. The current date movement. PLEASE NOTE: In opened state from the mobile is used when sending this and in test mode the status LEDs are ACTIVE. parameter.
  • Page 7: Dali Groups 4: Lighting Zone B

    PD4-M-HCL 93006/93007 Soft Start 6. Smartphone App Commands Dim up to LUX set value for lighting zone A and broadcast 6.1. DALI Open DALI Starts DALI configuration mode 5.6. DALI groups 4: lighting zone B Automatic The operation mode of the detector can be Close DALI selected.
  • Page 8: Device

    PD4-M-HCL 93006/93007 Groups 1-4 7. Addressing and formation of groups Show / Check groupings In the group assignment process: Saves Before groups are formed, it is recommended that you draw up selected group of flashing DALI ECG a plan showing the grouping of all DALI electronic ballasts in the room.
  • Page 9: Step 2: New Addressing Process

    PD4-M-HCL 93006/93007 7.2. Step 2: New addressing process 7.3. Step 3: Check grouping and change if necessary Important note for slave operation: connect slave devices only after setting up addressing, or else ensure that, while auto- addressing takes place (all LEDs blinking quickly), no-one remains in any slave device’s detection area, so that no motion detection events are sent to the master.
  • Page 10: Adding Or Replacing Electronic Ballasts

    LUX. It may take up to 2 minutes, until the new adjustment shows effect. • Step 4: Use the + / - buttons in the smartphone app for minimal corrections 10. Article Type Part.-Nr. PD4-M-HCL-FC 93006 PD4-M-HCL-SM 93007 IR-Adapter 92726 Accessory (optional) PD4-S-DAA4G-FC...