Configuration
4.7 Configuring a SINAMICS drive in S7T Config
Step
Activity
15
Select parameter "p210" and enter "400".
The Smart Line Module and the Motor Module of the SINAMICS S120 training case have been especially
equipped for operation on a 230 V system. For this reason, "Parameter p210" of the connected drives must be
set to the following value, which differs from the factory settings:
p210 = 400 V device connection voltage SERVO/VECTOR
The setting of "parameter p210 = 400 V" cannot be calculated by the SINAMICS operating system and has been
pre-assigned for error-free operation of the SINAMICS S120 training case on the 230 V system.
16
To configure the parameter "p1248" (DC link voltage low threshold), open the tree structure SIMATIC 300(1) >
Technology > S120_CU320_2_DP > Drives > Servo_02 > Configuration in the project navigator.
In the "Motor data" field, select the "No calculation" setting.
58