Trouble Shooting Charts - Onan MJA Series Service Manual

Electric generating plants
Table of Contents

Advertisement

72
STARTING SYSTE M
TROUBLE-SHOOTING CHART 7 (Cont.)
I
,
Replace bearings.
f
(cont.)
I
Slo"w starter "
!Worn bearings.
I
Burned solenoid contacts.
I
Replace.
i
I
Open or shorted field
I
windings.
I
Replace windings.
J
!
i
Battery discharged Defective charging circuit
See Sect 6
· 1
<'
I
I
Defective stArting circuit
Check starter circuit
I
J.
"
~
I
Adjust starting pro­
cedures, check for
causes of hard starting
Excessive use of starter
I
Dirt and electrolyte on
I
Clean battery top.
constant drain.
I
I
top of battery causing
, ,
Replace.
I
Defective battery.
I
Defective batter:y"!,
Hardened plate::; (sulfation)
due to low charge after
long period.
Replace battery, check
new battery charge
Shorted cells.
condition at frequent
intervals.
Loss of active material.
I
Broken terminals.
Starter won't
Defective ring gear or
Replace ring gear or
i
engage flywhee 1
1\
pinion.
pinion.
L
I
I
Pinion clearance too great Adjust pinion clear ­
(early models only).
ance (Fig3.S.D).
I
" Incorrect starter position
Adjust position with
I
(early models only);
shims, Sect 3. S. 5.
I
t -
When a battery fails, don't be satisfied just replacing it. Findthe
cause of the failure and make the necessary repairs.