Onan MJA Series Service Manual page 13

Electric generating plants
Table of Contents

Advertisement

- - -
11
TROUB LE -SHOOTING CHAR T
TROUBLE-SHOOTING CHART 1, THE ENGINE
TROUBLE
Engine will not
crank
I
Engine cranks
too slowly
Engine cranks but
won't start
Water in fuel.
Replace fuel.
I
­
REMEDY
POSSIBLE CAUSE
Battery discharged.
See Trouble-Shooting
Chart 7.
Control circuit defective .
See Sect 6.
Internal seizure.
Disassemble engine
and repair.
Engine oil too heavy for
See Sect 3.5.1 for oil
operation in low temper-
recommendations.
ature .
Defective connections be-
See Sect 3.6.2.
tween battery and starter.
!
REVOLVING ARMATURE
GENERA TOR (Exciter
Cranked)
Poor brush contact on
See Sect 5.
generator.
SEPARATE STARTING
MOTOR MODELS
Starting motor de-
See Trouble -Shooting
fective.
Chart 7.
Oil in crankcase too
See Sect 3.5.1 for oil
heavy for low temper-
recommendations.
ature.
Discharged battery.
See Trouble-Shooting
Chart 7.
Corroded battery con-
See Sect 3.6.2.
nectj Jns or defective
battery cable.
Fuel system faulty.
No fuel in tank.
Refill tank.
Clean filter Sect 3.2.2
Filter screen clogged.

Hide quick links: