Onan MJA Series Service Manual page 107

Electric generating plants
Table of Contents

Advertisement

L
:?"
REVO L V IN G FTEL D GKN ERA T O R f . 0 5
TROUBLE SHOOTING CHARTlO, REVOLVING FIELD GENERATOR
TRO'UBLE
PROBAB.L$. CAUSE
REMEDY
. Engine runs but volt-
Residual magnetism gone See Sect 4. 3.1 for
age won't build up
trouble shooting.
Dead short in load.
Inspect load and cor­
rect.
Magneciter defective,
See Trouble..;Sbooting-
Chart 11 -Magneciter
Open circuit,ground or
Test as per Sect 4.3.2
short in stator.
Replace
if
necessary .
Open circuit, ground or
Test as per Sect 4.3.2
short in revolving field.
Replace
if
necessary .
Current unsteady but
Loose connection .
Clean and tighten Con-
engine speed not
nections.
fluctuating
Poor brush contact.
Reseator replace
brushes. Clean Slip
rings .
Frequency drops under Low engine power.
'See Trouble..;ShoOting;
heavy load
Chart 1 -Engine
Poor governor adjust-
Adjust engine gover­
ment.
nor Sect 3. 4
Voltage drops under
Defective Magneciter.
See Trouble-Shooting
hea vy load, little
Chart
11 -
Magneciter
fre.quency change.
Generator won't de-
Unbalanced load on lines. Adjust loa d.
liver rated current.
Defective Magneciter.
See Trouble-Shooting
Chart ll-Magneciter
Defective field windings.
Test and replace if
defective
Generator overheats.
Overloaded.
Reduce Load.
Partial short in load.
Correct short.
Poor ventilation.
Increase ventilation,
..