Onan MJA Series Service Manual page 56

Electric generating plants
Table of Contents

Advertisement

54
1'"" N 1
·.r
1 UN S Y S
'l'
~
M
~~~~~~~--~~~~~----------~---------------
TROUBLE-SHOOTING CHART 4, • IGNITION SYSTEM
TROUBLE
POSSIBLE CAUSE
REMEDY
No spark
No voltage to ignition
Check control system
system.
Sect 6.
Defective breaker points.
I
Inspect points for dirt,
burning, pitting. Check
clearance.
Defective high tension
I
Replace.
leads.
Defective spark plugs.
Replace.
High resistance in
Replace.
primary leads.
Defective. ignition coil.
Replace.
Weak, Yellow
Dirty, burned or pitted
Clean or replace the
Spark - usually
breaker pOints.
points.
causinghatd
starting
Defective ignition con­
Test and replace
if
denser.
defective
High resistance in
Clean aU connections
primary circuit.
and inspect the wiring.
Defective spark plugs.
Replace.
Weak ignition coil.
Replace.
Excessively
I
High voltage.
Be sure correct voltage
Burned or Pitted
batteries are used.
Ignition Points
Dirty or oily points.
Keep points clean ata11
times - don't over oil
cam and pivot.
Breaker gap too small
<
Adjust.
Defective ignition con­
Check the condenser on
denser.
a commercial tester.
Using the wrong i'gnition
Use only the condenser
condenser.
specified.