Short Circuit Protection Recommendations - Toshiba H9 Quick Start Manual

Adjustable speed drive
Table of Contents

Advertisement

Short Circuit Protection Recommendations

Table 13. 230/240 and 400/480-Volt ASD Recommended Circuit Breaker Selection.
Model Number
VT130H9U
2010
2015
2025
2035
2055
2080
2110
2160
2220
2270
2330
2400
2500
2600
2750
210K
212K
4015
4025
4035
4055
4080
4110
4160
4220
4270
4330
4400
4500
4600
4750
410K
412K
415K
420K
425K
430K
435K
440K
86
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Continuous Output Current
HP
(Amps)
0.75
3.2
1.0
4.2
2.0
6.8
3.0
9.6
5.0
15.2
7.5
22.0
10
28.0
15
42.0
20
54.0
25
68.0
30
80.0
40
104
50
130
60
154
75
192
100
248
125
312
1.0
2.1
2.0
3.4
3.0
4.8
5
7.6
7.5
11.0
10
14.0
15
21.0
20
27.0
25
34.0
30
40.0
40
52.0
50
65.0
60
77.0
75
96.0
100
124
125
156
150
180
200
240
250
302
300
361
350
414
400
477
Circuit Breaker Part Number
HLL36015
HLL36025
HLL36040
HLL36050
HLL36070
HLL36090
HLL36100
HLL36125
HLL36150
JLL36200
JLL36250
LIL36300
HLL36015
HLL36025
HLL36040
HLL36070
HLL36090
HLL36100
HLL36125
HLL36150
JLL36200
JLL36225
JLL36250
LIL36300
LIL36400
LIL36450
LIL36500
Consult NEC
H9 ASD Quick Start Guide

Advertisement

Table of Contents
loading

Table of Contents