Short Circuit Protection Recommendations - Toshiba G9 ASD Quick Start Manual

True torque control2 adjustable speed drive
Hide thumbs Also See for G9 ASD:
Table of Contents

Advertisement

Short Circuit Protection
Recommendations
Table 9. 230/240 and 400/480-Volt ASD Recommended Circuit Breaker Selection.
Model Number
VT130G9U
2010
2015
2025
2035
2055
2080
2110
2160
2220
2270
2330
2400
2500
2600
2750
210K
4015
4025
4035
4055
4080
4110
4160
4220
4270
4330
4400
4500
4600
4750
410K
412K
415K
420K
425K
430K
435K
G9 ASD Quick Start Guide
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
HP
Continuous Output Current (Amps)
0.75
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
Circuit Breaker Part Number
3.5
4.8
8.0
10.0
17.5
27.5
33
54
66
76
90
120
152
176
221
285
2.7
4.1
5.8
10.5
14.3
17.6
27.7
33
41
48
66
79
94
116
160
179
215
259
314
387
434
HLL36015
HLL36015
HLL36015
HLL36025
HLL36025
HLL36040
HLL36050
HLL36070
HLL36090
HLL36100
HLL36100
HLL36125
HLL36150
JLL36200
JLL36250
LIL36300
Consult NEC
HLL36015
HLL36015
HLL36025
HLL36040
HLL36050
HLL36070
HLL36090
HLL36100
HLL36100
HLL36125
HLL36150
JLL36200
JLL36225
JLL36250
LIL36300
LIL36300
LIL36400
LIL36400
LIL36450
LIL36500
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents