6.2

4 ZONE PANEL

Mains on (Battery voltage at 24 volts, control voltage at 28 volts)
Quiescent current:
Alarm current:
Max. zone current:
Min zone current:
Mains on (Battery voltage at 24 volts, control voltage at 23.1 volts)
Quiescent current:
Alarm current:
Max. zone current:
Min. zone current
Mains on (Battery voltage at 18 volts, control voltage at 17.8 volts)
Quiescent current:
Alarm current:
Max. zone current:
Min. zone current:
6.3
8 ZONE PANEL
Mains on (Battery voltage at 24 volts, control voltage at 28 volts)
Quiescent current:
Alarm current:
Max. zone current:
Min zone current:
Mains on (Battery voltage at 24 volts, control voltage at 23.1 volts)
Quiescent current:
Alarm current:
Max. zone current:
Min. zone current
Mains on (Battery voltage at 18 volts, control voltage at 17.8 volts)
Quiescent current:
Alarm current:
Max. zone current:
Min. zone current:
TM0066
111 mA
237 mA
45 mA
10 mA
87 mA
179 mA
40 mA
10 mA
70 mA
137 mA
29 mA
10 mA
152 mA
282 mA
45 mA
10 mA
87 mA
128 mA
40 mA
10 mA
99 mA
151 mA
30 mA
10 mA