The 8, 16 and 32 zone control panels have three switches which are designated as follows:-
PROCRST
-
FCRST
-
Example:
Zones 1, 3, 5 and 7 fault LED's illuminated would indicate a total of 85 failures.
Operation of the ' FCRST' switch will reset the counter to zero.
Ensure that leaf 4 of SW1 is returned to the off position.
TM0066
Operation of this button will re start the processor in the event of a total
failure.
Operation of this button will clear the processor failure counter to zero.
To check how many times the processor has automatically been restarted
place leaf 4 of SW 1 to the on position and the first eight zonal fault
LED's will illuminate in a binary format to indicate the number of
processor failures.
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
Page 26 of 39
= 1
= 2
= 4
= 8
= 16
= 32
= 64
= 128
Issue 2.01