Status Number; Command Overview - EUCHNER EKS Manual

Electronic-key-system adapter with ethernet tcp/ip interface
Hide thumbs Also See for EKS:
Table of Contents

Advertisement

Manual EKS Electronic-Key Adapter Ethernet TCP/IP
8.4

Command overview

Description
Program Electronic-Key
Read Electronic-Key
(also read the serial number)
Read the Electronic-Key status
8.5
Status numbers
Value
Description
00
No error
hex
02
Electronic-Key not in the operating distance
hex
03
Parity bit error on read-only Electronic-Key
hex
06
Write process interrupted. Start address or number of bytes is not a multiple of the block size 4
hex
Read attempt when the Electronic-Key adapter is set to read/write Electronic-Key and a read-only
17
hex
Electronic-Key is inserted
Read attempt when the Electronic-Key adapter is set to read-only Electronic-Key and a read/write
18
hex
Electronic-Key is inserted
4x
General Electronic-Key communication error (renewed write or read process necessary)
hex
50
Write attempt despite enabled write protection
hex
61
Maximum permissible number of TCP/IP connections exceeded
hex
2100420-03-05/19
Command message
TP (see chapter 8.3.1)
TL (see chapters 8.3.2 and 8.3.3)
Ek (see chapter 8.3.4)
Subject to technical modifications
Reply message
RF (see chapter 8.3.1)
RL (see chapter 8.3.2)
or
RF (see chapter 8.3.2)
Ek (see chapter 8.3.4)
Page 31/34