Dunkirk EXCELSIOR Series Installation, Operation & Maintenance Manual page 53

High efficiency oil fired hot water boiler
Hide thumbs Also See for EXCELSIOR Series:

Advertisement

Steps to inspect, c leanand/orreplace control w ell:
1.
Turn off electric service to boiler controls.
2.
Drain boiler water to level below tapping for control
well.
3.
Remove low water cut-off/limit
sensor from control
well.
4.
Unscrew control well from tapping.
5.
Inspect portion of control well exposed to water for
scale or sediment buildup.
6.
Light deposits may be removed by wiping control well
with damp cloth.
Wiping probe with cloth soaked in
vinegar will remove more tenacious lime deposits.
7.
Clean pipe threads of probe to remove old, hardened
pipe dope and other foreign matter.
8.
Apply moderate amount of good quality pipe dope to
pipe threads on control well, leaving two end threads
bare.
Do not use PTFE (Teflon) tape.
9.
Reinstall control well into tapping.
10. Reinsert low water cutoff/limit
sensor in control well
and secure with grommet.
11. Fill system with water and purge.
12. Restore electric service to boiler.
13. Fire burner to heat water in boiler 180°F to drive off
free oxygen.
14. Warning - before returning
boiler to service:
Follow
low water cut-off test procedure in Figure 36, Page 41.
• Continue to circulate water for few hours.
• Stop firing boiler.
• Drain system in manner and to location that hot water
can be discharged safely.
• Remove plugs from all available returns and wash
water side of boiler as thoroughly
as possible, using
high-pressure
water stream.
• Refill system with fresh water.
3.
Add appropriate
boiler water treatment
compounds
as recommended
by your qualified water treatment
company.
4.
Testing pH/alkalinity
after boiler and system have
been cleaned and refilled as previously described, test
pH of water in system.
Can be done with pH test kit.
pH should be higher than 7 but lower than 11. Add
appropriate
water treatment
chemicals, if necessary, to
bring pH within specified range.
With this lower level of
protection,
care must be exercised to eliminate all free
oxygen in system.
5.
Boiler is now ready to be put into service.
18.10
Frequent
Water
Addition
Frequent water additions, although unusual for water boiler,
are sign of leaky system.
Excessive amounts of make up
water supplied to boiler can significantly
shorten life of
boiler. Amount of water varies with contamination
level of
water.
Repair leak and consult with your water treatment
specialist for recommendations.
18.9
Boiler
And System
Cleaning
Instructions
For Trouble
Free Operation
1.
Boiler and system (other than expansion tank) must
be full of water for satisfactory
operation. Add water
to system until boiler pressure gauge registers
12 psi.
Water should come out of all air vents when opened.
2.
Wash Oil and grease which accumulate
in new hot
water boiler out in following manner:
• Shut off valves have been installed between boiler
return manifold and system, to minimize amount of
system draining.
• Drain boiler to level below relief valve tapping.
• Remove relief valve using extreme care to avoid
damaging it.
• Add appropriate
amount of recommended
boil out
compound.
• Replace relief valve.
• Fill entire system with water and purge.
• Start firing boiler.
• Circulate water through entire system.
• Vent system, including radiation.
• Allow boiler water to reach operating
temperature,
if
possible.
18.11
Attention
To Boiler
While
Not In Operation
Fully drain boiler if not used during
winter
months
to prevent
freeze damage.
1.
Keep manual fuel supply valve shut off if burner is shut
down for extended period of time.
2.
To recondition
heating system in fall season after
prolonged shut down, follow instructions
outlined in
See "15 - Filling boiler" on page 38.
3.
Boiler contains controls which may cause boiler to shut
down and not restart without service. If damage due
to frozen pipes is a possibility,
heating system should
not be left unattended in cold weather;
or appropriate
safeguards and alarms should be installed on heating
system to prevent damage if boiler is inoperative.
4.
Keep boiler and area around it clean. Never burn
refuse or any material other than specified fuel in your
boiler.
Have your boiler checked each year by qualified
service agency.