Dunkirk EXCELSIOR Series Installation, Operation & Maintenance Manual page 46

High efficiency oil fired hot water boiler
Hide thumbs Also See for EXCELSIOR Series:

Advertisement

Figure
39
- Beckett
Electrode
Tip Adjustments
Standard
Dimensions
(L1, V1)
Heads
5/32 '*Gap ,_
Figure
40
- Beckett
Electrode
Tip Adjustments
Standard
Dimensions
(L2)
Heads
5/32 Gap ......
Figure
41
- Beckett
Check/Adjust
"Z"
Dimensions
L1 8= L2 Heads
L1/L2
Heads
See Figure 39. The important
"Z" dimension is distance
from leading edge of head to end of air tube. This distance
for L1 & L2 heads is 1-3/8" if the tube has a straight shroud
or 1-3/4" if air tube has conic shroud. "Z" dimension is fac-
tory set for burners shipped with air tube installed. Even if
factory set, verify "Z" dimension has not been changed.
1.
Use following procedure to adjust "Z" dimension,
if it is
not correct:
Turn off power to burner.
Disconnect oil connector tube from nozzle line.
Refer to figure above. Loosen splined nut from nozzle
line. Loosen hex head screw securing escutcheon
plate to burner housing.
Place end of ruler at leading edge of head and, using
straight edge across end of airtube, measure distance
to end of tube. A Beckett T501 gauge may also be
used.
Slide nozzle line forward or back until this dimension
is 1-3/8" for L1 & L2 heads if tube has straight
shroud, or 1-3/4" if air tube has conic shroud.
Tighten hex head screw to secure escutcheon plate to
burner chassis. Then tighten splined nut and attach
oil connector tube.
2.
Recheck"Z"
dimension periodically when servicing to
ensure escutcheon plate has not been moved. Reset
"Z" dimension if you replace air tube or nozzle line
assembly.
Figure
42
- Check/Adjust'Z"
Dimension
- V1
Heads
Vl heads
See Figure 40. The important
"Z" dimension is distance
from leading edge of head to end of air tube. This distance
for Vl heads is 1-3/4". "Z" dimension is factory set for
burners shipped with air tube installed. Even if factory set,
verify "Z" dimension has not been changed.
1.
Use following procedure to adjust "Z" dimension, if it is
not correct:
Turn off power to burner.
Disconnect oil connector tube from nozzle line. Refer
to figure above. Loosen splined nut from nozzle line.
Loosen hex head screw securing escutcheon plate to
burner housing.
• Loosen acorn nut. Hove head adjusting
plate until
"0" lines up with reference indicator on housing, and
tighten hex head screw. Place end of ruler at leading
edge of head and, using straight edge across end of
air tube, measure distance to end of tube. A Beckett
T501 gauge may also be used.
• Slide the nozzle line forward or back until this
dimension is 1-3/4" for Vl heads. Tighten acorn nut.
• Tighten hex head screw to secure head adjusting
plate to burner chassis. Then tighten splined nut and
attach oil connector tube.
2.
Recheck"Z"
dimension periodically
when servicing to
ensure escutcheon plate has not been moved. Reset
"Z" dimension if you replace air tube or nozzle line
assembly.