Dunkirk EXCELSIOR Series Installation, Operation & Maintenance Manual page 52

High efficiency oil fired hot water boiler
Hide thumbs Also See for EXCELSIOR Series:

Advertisement

Before servicing,
turn
off electrical
power
to boiler
at service
switch.
Turn off fuel supply
to burner
Failure to comply
will result in death
or serious
injury.
Perform
regular
service
and
maintenance
by
qualified
service
agency
at least
once
every
12
months
to assure
safe,
trouble
free
operation
and
maximum
efficiency.
Verify
proper
operation
after servicing.
18.1
Annually
Recommend qualified Service Agency check at lease once a
year:
• Flue passages,
• Combustion chamber area (target wall, fire door
insulation)
• Burner adjustment,
• Operation of the controls,
• Boiler seals (fire door gasket or silicone seal, cast iron
sectional seals, flue collector)
Before start of each heating season (or system has been
shut down for extended period of time)
• Recheck whole system for water, oil, and vent piping
leaks.
• Replace or patch any leaks or seals that are faulty
• Inspect flue ways at least once a year- Preferably at
start of heating season.
• Inside of combustion chamber.
• Clean vent system and boiler flue ways if soot or scale
has accumulated.
When cleaning, take precaution
to avoid damage to burner swing door insulation.
If
damaged, or if there is evidence of previous damage,
burner swing door insulation must be replaced
immediately.
• Oil Burner and controls.
18.2 Vent Pipe
Visually inspect entire venting system once a month for any
signs of leakage, deterioration,
or soot build up.
If vent pipe shows any signs of leaking or deterioration,
replace it immediately.
If it shows any signs of soot build up, clean vent pipe and
have burner settings and combustion checked by qualified
service agency.
18.3 Relief Valve
• Test relief valve for proper operation.
Refer to valve
manufacturer's
instructions
packaged with relief valve.
18.4
Conventional
Expansion
Tank
See "Equipment
And Accessories" section.
18.5
Diaphragm
Expansion
Tank
See "21 - Equipment And Accessories" on page 58.
18.6 WATER SYSTEM
Drain system completely if system is to remain out of
service during freezing weather.
Water left in system will
freeze and crack pipes and/or boiler.
18.7 Oil Burner
Maintenance
Beckett AFG, perform following preventative
maintenance
annually, preferably prior to heating season.
• Fuel Filter
Replace to prevent contaminated
fuel from
reaching nozzle. Partially blocked fuel filter can cause
premature failure of fuel pump.
• Fuel Pump Unit Replace pump screen and clean pump
unit to maintain fuel delivery to nozzle.
• Ignition
Electrodes
Clean and adjust as per
manufacturer's
recommendations,
so as to maintain
reliable ignition of oil.
• Nozzle
Replace so as to maintain safe and reliable
combustion efficiency. Always replace with exact nozzle
as required in charts. See "17 - Oil Burner, Nozzle, &
Air Settings" on page 46.
• Fan and Blower
Housing
Keep clean, free of dirt, lint
and oil to maintain proper amount of air fuel requires to
burn.
• Check burner
settings
and adjust
as needed.
NOTE-" If any component parts must be replaced, always
use parts recommended
by burner manufacturer.
18.8 Maintenance
Of Optional
Low Water Cut Off
Burn and scald hazard.
Verify
boiler is at zero
pressure
before
removing
relief valve or control
well.
Open safety
valve to relieve
all internal
pressure
prior to proceeding.
Remove control well from top of rear boiler section every
five years and clean any scale or sediment deposits from all
parts exposed to boiler water.