M-system R3-NM3 Instruction Manual page 7

Modbus interface module, for temperature control module
Table of Contents

Advertisement

TRANSMISSION DATA ASSIGNMENTS
DIP SW located at the side of the module specifies each I/O module's data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
Module 7
Then the I/O data are assigned as in the table below:
Input Registers (3X)
1 – 4, 257 – 264
Holding Registers (4X)
5 – 8, 265 – 272
9 – 12, 273 – 280
13, 281 – 282
14, 283 – 284
15, 285 – 286
16, 287 – 288
For Coil (0X) and Inputs (1X), addresses 16 times assigned data areas (Data Allocation Type) are allotted with the Data Al-
location Type '1' and '4.' With '8' and '16,' 64 (4 × 16) are automatically assigned.
MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
Shows each module's availability and error status.
15
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4 and US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). Negative percentage is represented in 2's
complements.
15
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4 and US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2's complements.
15
4
4
4
1
1
1
1
ADDRESS
POSITION
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
0
0
0
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
Coil (0X)
Inputs (1X)
Module 1
Module 2
Module 3
:
Module 16
R3-NM3
ADDRESS
POSITION
1 – 64
Slot 1
65 – 128
Slot 2
129 – 192
Slot 3
193 – 208
Slot 4
209 – 224
Slot 5
225 – 240
Slot 6
241 – 256
Slot 7