Delayed Input & Timed Output; Delayed Input & Pulsed Output; And / Or Conditions; Input And Output Timers - Keyscan Aurora IOCB1616 Installation Manual

Table of Contents

Advertisement

06 – Delayed Input & Timed Output
Example: Monitoring – Monitor a stairwell door.
Input 6 is defined as the stairwell door; Output 6 is defined as the stairwell door siren. If
the stairwell door is opened, the alarm notification to the guard's computer is delayed by
the specified input delay time. Output 6 will not activate until the input time has expired;
the siren remains on for the duration of the specified output time. It does not reset until
the input is secured.
07 – Delayed Input & Pulsed Output
Example: Monitoring – Monitor a stairwell door.
Input 7 is defined as the stairwell door; Output 7 is defined as the stairwell door siren. If
the stairwell door is opened, the alarm notification to the guard's computer is delayed for
the specified input delay time. Output 7 will pulse on and off for the duration of the
specified output time. It does not reset until the input is secured.

And / Or Conditions

When assigning two or more inputs to an output, one of the following logic conditions must
be specified:
"Or" Condition
With the "OR" condition, when multiple inputs are assigned to a common output, any one
input fires the output.
"And" Condition
With the "AND" condition, when two multiple points are assigned to any common output,
both points need to go to an alarm state to fire the output.
You cannot have more than 2 inputs assigned to an output with an "AND" condition. You
may have multiple sets of 2 inputs that use an "AND" condition assigned to the same
output. An example would be Input 1 "AND" Input 2 assigned to Output 1 as well as Input
3 "AND" Input 4 assigned to Output 1.

Input and Output Timers

Input Timer – sets the delay time from the point the input is tripped. The range of time is
from 00 seconds to 240 seconds. (00 seconds is no delay.) The Input Timer applies only on
Modes 4 to 7.
Output Timer – sets the delay time from the point the output is tripped or the amount of
time the output is enabled or activated depending on which of the 7 modes is selected. The
range of time is from 00 seconds to 240 seconds. (00 seconds is no delay.)
Schedule Inputs and Outputs
In the Aurora software you can assign a schedule to an input or output.
Input – assigning a schedule enables/disables or arms/disarms the input based on the
schedule
Output – assigning a schedule to an output turns it off or on based on the schedule
Keyscan Inc. A Member of the Kaba Group
4