System Jumper J16 on ACU
The following table outlines jumper settings on the ACU circuit board for enabling
inputs/outputs on J16.
KI-00142E-07-11
System Jumper J16 Inputs/Outputs
PC1094 – PC1095 Circuit Boards
PC1097 or Later Circuit Boards
The Enable/Disable IOCB1616 function for PC1097 or later control boards is set in the
Aurora software from the Hardware Setup > Additional Settings screen under the Hardware
Settings heading. To enable the control board for an IOCB1616 connection, click in the box
to the left of IOCB. When enabled, the box has an x.
Current Supply and Current Load
The following table lists circuit board and power supply data.
Current Supply and Current Load
Board
DPS-15
DPS-15
ACU
OCB-8
IOCB1616
IOCB1616
Does not include communication board current draw.
Keyscan Inc. A Member of the Kaba Group
System Jumpers J16
J16 -
1
2
S Y S T E M C O N F I G .
J16 -
A
B
Jumper
Jumper Off
Settings
Off = 0
Disable IOCB1616
Enable IOCB1616
Description
ACU - 12 Volts DC output
AUX – 12 Volts DC output
Current draw
Current Draw
No outputs connected
With outputs connected
3
4
5
6
7
8
C
D
E
F
G
H
Jumper On
On = 1
Jumper #
8
8
Jumper Setting
Off=0 / On=1
1
0
Current
1.2 A
1.2 A
130 mA
230 mA
100 mA
400 mA
12