Table 6-3 Drive And Motor Connection Terminals; Figure 6-5 Connection Of The Supply-System Power Cable - Siemens SINAMICS SM150 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Note
To route the power cables from above into the cabinet, remove the cover plate at the top of
the cabinet.
NOTICE
Danger of thermal damage
Inadequately fastened cables at the connection point represent a high electrical transfer
resistance that can cause thermal damage (contact erosion) during operation.
Tighten the screws with the specified torque.
1. Screw the protective ground at the provided locations in the cabinet to the appropriate
2. Connect the infeed cable to the supply-system connection busbar.
3. Screw the individual phases of the motor cable to the connections below of the output
Direction of motor rotation
Connect asynchronous machines with clockwise phase sequence (looking at the drive shaft)
to the drive as follows:
Table 6-3
In contrast to the connection for the clockwise phase sequence, two phases have to be
reversed with a counter-clockwise phase sequence (looking at the drive shaft).
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017
connection with the ground symbol.
Note
Connect the motor cables first and then the power cables.
Figure 6-5
Connection of the supply-system power cable
phases.
Observe the following connection sequence of the conductors: U1, V1, W1
Drive and motor connection terminals
Drive (connection terminals)
U2/T1
V2/T2
W2/T3
Electrical connection
6.5 Connection
Motor (connection terminals)
U
V
W
115