Diagnostics and troubleshooting

11.1

What to do in case of failure?

After switching on the muting controller, the display elements (see chapter 3.2 "Display elements") assist in
checking the correct functionality and in fault-finding.
In case of failure, you can read a message from the 7-segment display. With the error message you can
determine the cause of the error and initiate measures to rectify it.
NOTICE
If the light curtain responds with an error display, you will often be able to eliminate the
cause yourself!
Ä Switch off the machine and leave it switched off.
Ä Analyze and eliminate the cause of the fault using the following table.
Ä If you are unable to rectify the fault, contact the Leuze electronic branch responsible for you
or call the Leuze electronic customer service (see chapter 12 "Service and support").
With the Sensor Studio diagnostics software, you can create a service file that you can send to Leuze elec-
tronic customer service in the event of service requests (Diagnostics software Sensor Studio). The service
file contains all available information on the muting controller, as well as configuration and settings.
11.2

Error messages 7-segment display

User messages/notes and error messages are indicated by the alternating display of a letter and a two-digit
number.
Tab. 11.1:
Messages of the 7-segment display (F: internal device error, E: external error, U: usage info during appli-
cation errors)
Error
F[No. 0-255]
OFF
E01
E02
E03
E04
E05
E06
E07
E08
E09
Leuze electronic
Cause/description
Internal error
Very high overvoltage (± 40 V) Supply the device with the correct
Cross connection between
OSSD1 and OSSD2
Overload on OSSD1
Overload on OSSD2
High-impedance short circuit to
VCC OSSD1
High-impedance short circuit to
VCC OSSD2
Short circuit against GND at
OSSD1
Short circuit against +24 V at
OSSD1
Short circuit against GND at
OSSD2
Short circuit against +24 V at
OSSD2
Remedies and measures
In the event of an unsuccessful
restart, contact customer service.
voltage.
Check the wiring between OSSD1
and OSSD2.
Check the wiring or exchange the
connected component (reducing
the load).
Check the wiring or exchange the
connected component (reducing
the load).
Check the wiring. Exchange the
cable, if applicable.
Check the wiring. Exchange the
cable, if applicable.
Check the wiring. Exchange the
cable, if applicable.
Check the wiring. Exchange the
cable, if applicable.
Check the wiring. Exchange the
cable, if applicable.
Check the wiring. Exchange the
cable, if applicable.
MSI-MD-FBX
Diagnostics and troubleshooting
Behavior of the
muting controller
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
36