DIP
switch
7/8
Muting timeout
Setting the operating mode
The following table lists the permissible operating modes that can be set via the DIP switch blocks.
After the device is started, the 7-segment display of the muting controller shows the set operating mode.
NOTICE
This muting controller can only be operated in operating mode 7.
NOTICE
Error in event of impermissible setting of DIP switches!
If a DIP switch configuration is set that does not correspond to that of a permissible operating
mode, an operating mode error is triggered and the OSSDs switch off.
Ä Only set one of the DIP-switch configurations listed in the operating mode table.
NOTICE
Restart interlock for access guarding!
For access guarding, a restart interlock is required.
Ä If the automatic restart interlock is configured in the muting controller, you must carry out the
restart interlock, e. g. via the machine interface.
Tab. 8.2:
Operating modes
DIP
switch
Function
Number of
muting sen-
Operating
mode
7
2-sensor
Leuze electronic
Function
1
2
Muting mode
sors
Timing con-
trolled
Starting up the device - Configuration
ON
OFF/OFF: 20 seconds
OFF/ON: 2 minutes
ON/OFF: 10 minutes
ON/ON: 100 hours
3
4
EDM
Restart
Without
Manual
MSI-MD-FBX
OFF
5
6
Muting-en-
Muting-time-
able
out exten-
sion
With
Without
32