Oil return measures
If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed
for every 2.5 metres of height
difference.
Oil return measures
Outdoor
component
Oil pump bend
in suction pipe to
outdoor component
1 x every 2.5
metres of rising
pipe
Radius:
min. 50 mm
Indoor unit
Mounting points for wall bracket
MD 261 IT
65
45
MD 351 IT
65
45
Connection variations of
inner unit
Connection variations
1
2
1 Outlet on the wall, right
2 Outlet through the wall, right
3 Outlet through the wall, left
4 Outlet on the wall, left
Wall bracket for indoor unit
The wall bracket for the unit must
be attached with suitable screws
and anchors.
65
750
65
815
All dimensions in mm

Installation

NOTE
Installation should only be
performed by authorised
specialists.
Unit installation
The indoor unit is attached by
means of a wall bracket, under
consideration of air discharge side
3
4
located in the lower part.
1. Mark the mounting points
on the statically permissible
building sections according to
the dimensions of the unit.
2. If necessary, remove the break
out opening on the housing.
3. Connect the refrigerant
pipes, electrical cables and
condensation pipe to the indoor
unit as described below.
4. Hang the indoor unit onto the
wall bracket by tilting it back
slightly and by pressing the
bottom part of the unit against
the bracket (Figure 5).
5. Check that the unit is level.
5
Hooking in
19