Jumper assignment of the incremental encoder matching module
Assuming that an encoder with a symmetrical line (5 V input voltage) is used (providing two–
phase displaced pulse sequences) and that the evaluation of two signal edges is selected, then
the following jumpers and components must be soldered in (configuration at delivery):
R4, R6, R7, R9, R12, R14
Solder jumpers:
Capacitors:
Cl, C2, C5 (1 O nF for all)
Resistor R11:
2.2 kQ (for a 24 V voltage at the prelimina~ contact)
open
DIP switch S2.1:
DIP switch S1
2
3
4
5
II
II
The encoder matching module is inserted into the slot for channel 1.