Siemens SIMATIC S5 Equipment Manual page 163

Digital position decoder ip 241 with fb 156/1 57 158
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Programming Instructions
Inhibit interrupt (IS)
Inhibit interrupt for supplying new setpoints to the module (IV)
Inhibit interrupt depending on direction (RV)
Calculate average value (MB)
Verify-read (PR)
Parametrize the working data block as shown below.
I
DW n
Track number
DW n+l
DW n+2
DW n+3
Track identifier bits, channel 1
DW n+4
Track identifier bits, channel 2
DW n+5
Assigned
DW n+6
O or 255
DW n+7
*) This parameter is used for PLCS S5–150U/S and S5–155U in 150U mode during interrupt
processing (see section 9.4.8).
The track number (DL n+l) can be disregarded for the IS, IV, RV, MB and PR functions.
The data block number of the user data block (DR n+l) must be the same data block number
used also during startup in connection with function block FB 156.
See the description of function block FB 157 (section 9.3.7) for more details on handling the "inhib-
it interrupt" and "inhibit interrupt for supply" functions.
9 – 42
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
IS, IV, RV, MB or PR
User DB
I
ST parameter
I
Alarm bit O to 7
I
I
KS
Input
Input
KY
Unaffected
Unaffected
KM
output
I
KM
output
KM
Output of control bits
Input *)