Operating Modes
Man (Manual): Reset by pushing
button in. (Standard Offering)
Trip: Push and turn reset button
counterclockwise to manually trip.
This action causes N.O. and N.C.
contacts to change state. Releas-
ing button reverts device to
manual mode.
ATTENTION: Do not use automatic reset mode in applications where unexpected automatic restart of the
motor can cause injury to persons or damage to equipment.
Figure 3. Contact Status
Adjustments
To adjust trip current, turn dial until the desired current is
aligned with the
pointer. Trip rating is 120% of dial setting.
Push to Test
Trip Indicator Window
Yellow indicator not visible: Not Tripped
Yellow indicator visible: Tripped
Figure 4. Trip Current Adjustment
IL04303001E
Series CEP7
Solid State Overload Relay
Auto: Push and turn reset button
to auto position. The relay resets
automatically — approximately
2 minutes after tripping.
(Optional Offering)
Trip: Push and turn reset button
counterclockwise to manually trip.
This action causes N.O. and N.C.
CEP7-M32__
contacts to change state. Releas-
CEP7-M37__
ing button reverts device to
CEP7-M45__
manual mode.
CEP7-M85__
CEP7-M110__
CEP7-M180__
Figure 5. Motor Current Rating
For more information visit: www.cutler-hammer.com
Instruction Leaflet
Effective: February 2002
CEP7-A32__
CEP7-A37__
CEP7-A45__
CEP7-A85__
CEP7-A110__
CEP7-A180__
Page 3

Advertisement

loading

This manual is also suitable for:

Cutler-hammer cep7-m32 seriesCutler-hammer cep7-a32 seriesCutler-hammer cep7-m37 seriesCutler-hammer cep7-a37 seriesCutler-hammer cep7-m45 seriesCutler-hammer cep7-a45 series ... Show all