V48A,F,J; V88A,J
SPECIFICATIONS • ORDERING INFORMATION
MODELS:
V48A (120 Vac) or V88A (24 Vac) solenoid operated
diaphragm valves for 1/2 or 1 psi [3.4 or 6.9 kPa]
maximum operating pressure.
V48F (120 Vac) solenoid operated diaphragm valve for
5 psi [34.5 kPa] maximum operating pressure.
V48J (120 Vac) or V88J (24 Vac) solenoid operated
diaphragm valves for 1 psi [6.9 kPa] operating pres-
sure and 150° F maximum ambient temperature.
TYPE OF GAS: Suitable for liquefied petroleum (LP), natu-
ral, manufactured, and sulfur-bearing gases.
VALVE CAPACITY: See table in Fig. 2.
VALVE PATTERN: Straight-through, nonoffset.
VALVE BODY MATERIAL: Die-cast aluminum.
PILOT TAPPING (see Table 1 for thread type): 3/4 through
1-1/2 inch valves: 1/8-27 NPT or 1/8-28 BSP.PI.
2 through 3 inch valves: 1/4-18 NPT or 1/4-19 BSP.PI.
BLEED TAPPING (see Table 1 for thread type): 1/8-
27 NPT or 1/8-28 BSP.PI.
VALVE OPENING TIME: Five seconds maximum at 2 oz/
2
in.
[0.86 kPa] pressure. Adjustable bleed valve assem-
bly or fixed bleed orifices available for longer opening
time (NPT threads only; see Accessories).
VALVE CLOSING TIME (on power failure; measured at
2
2 oz/in.
[0.86 kPa] pressure): 2 seconds maximum for 2
through 3 inch valves; 1 second maximum for 3/4 through
1-1/2 inch valves.
MAXIMUM OPERATING PRESSURE: See Table 1.
POWER CONSUMPTION (maximum): 9 watts or 15 VA.
AMBIENT TEMPERATURE RATING:
V48A,F and V88A: 32° F to 125° F [0° C to 52° C].
V48J and V88J: 32° F to 150° F [0° C to 65° C].
MAXIMUM FLUID TEMPERATURE:
V48A,F; V88A: 125° F.
V48J; V88J: 150° F.
THERMOSTAT HEAT ANTICIPATOR SETTING: For
60 Hz V88, set at 0.6A.
When purchasing replacement and modernization products from your TRADELINE
®
TRADELINE
catalog or price sheets for complete ordering number, or specify—
1. Order number.
2. Pipe size.
3. Operating pressure rating.
4. Transformer for V88.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000.
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales
Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2080—8
DIMENSIONS: See Fig. 1.
WEIGHT:
Pipe Size (in.)
3/4
1
1-1/4
1-1/2
2
2-1/2
3
APPROVALS: (60 Hz models only):
Underwriters Laboratories Inc. Listed: File No. MH1639;
Guide No. YIOZ.
American Gas Association Design Certified: Report
No. 21-7B.
Canadian Gas Association Certified: For use with natu-
ral, manufactured, and mixed gases (60 Hz models
only).
NOTE: All models rated at 50 Hz and all models with
BSP.PI threads are not AGA Design Certified.
OPTIONAL FEATURE: Valve position indicator is avail-
able on 1-1/4 in. V48A2227 and 2 in. V48F1103.
REPLACEMENT COIL ASSEMBLIES
116930: 24V, 60 Hz V88A
116931: 120V, 60 Hz V48A.
116932: 220V, 50 Hz V48A
116932: 240V, 60 Hz V48A
118888: 24V, 60 Hz V88J
139937: 120V, 60 Hz V48J
a
These V48/V88 bonnet assemblies and solenoid operators
are not compatible with old style valve bodies.

Ordering Information

®
wholesaler or your distributor, refer to the
5. Optional valve position indicator (1-1/4 inch and larger valves only),
if desired.
6. Replacement coil assembly, if desired.
7. Accessories, if desired.
2

Specifications

lb.
kg
2-1/2
1.13
3
1.36
3-1/2
1.59
4
1.81
9
4.08
8-1/2
3.86
9-1/2
4.31
a
: