By-Pass Monitor Or Pre-Heater Signal Output; Malfunction Monitor Output; Operation Monitor Output; When Switching Fan Speed Externally - Mitsubishi Electric LGH-25RVX-E Installation Instructions Manual

Lossnay energy recovery ventilator
Hide thumbs Also See for LGH-25RVX-E:
Table of Contents

Advertisement

Installation method (continued)
4

By-pass monitor or Pre-heater signal output.

By-pass monitor or Pre-heater signal can be selected at SW5-6.
(Refer to function settings
No. 58
Always check that it is the intended setting.
By-pass monitor SW5-6 OFF
By-pass operation
indicator
Max 240 VAC, 1 A
24 VDC, 1 A
Min
220 VAC, 100 mA
Power
5 VDC, 100 mA
Supply
Pre-heater output SW5-6 ON
2 m or more
Lossnay
OA
Pre-heater
Relay
Power Supply
Power Supply
for heater
for relay
CAUTION
• Select a duct heater in compliance with local and national
laws, ordinances, and standards.
Select a duct heater that has obtained the CE mark.
• Always select a heater that is equipped with a non-self-
resetting safety device.
Do not directly supply power from the Lossnay unit to the
duct heater.
(Doing so could cause fire.)
• Install a circuit breaker for the duct heater in compliance with
all applicable laws, ordinances, and standards.
• Install the duct heater separated from the product by a
distance of 2 m or more.
(Failure to do so may result in equipment damage due to the
transmission of residual heat from the heater.)
• When using a heater without a temperature control function,
select a heater with a capacity that is matched to the air
volume.
• Do not use the heater outside the set air volume.
(If the heater's capacity is too larger, this may result in the
heater frequently turning ON/OFF.)
(If the heater's capacity is too small, this may result an
inability to heat.)
• Ensure that the duct heater and Lossnay are wired and that
the Lossnay function settings have been configured, and then
always check operation by trial operation.
• For the duct heater output, see function setting SW5-6.
5

Malfunction monitor output.

TM3
Malfunction indicator
Power
Max 240 VAC, 1 A
Supply
24 VDC, 1 A
Min
220 VAC, 100 mA
5 VDC, 100 mA
)
TM3
7
8
9
X13
10
SA
TM3
7
8
9
X13
10
Max 240 VAC, 1 A
24 VDC, 1 A
Min
220 VAC, 100 mA
5 VDC, 100 mA
7
8
9
X14
10
6

Operation monitor output

Operation monitor output can be selected to sympathize with exhaust
fan or supply fan at SW 5-2.
SW5-2 OFF: Exhaust fan operation monitor output
SW5-2 ON: Supply fan operation monitor output
(Refer to function settings
No. 57
Always check that it is the intended setting.
TM3
Operation
indicator
Power Supply
Max 240 VAC, 1 A
24 VDC, 1 A
Min
220 VAC, 100 mA
5 VDC, 100 mA
To use operation monitor output for a supply after-heater, turn SW2-8
ON, and use the supply fan operation monitor output with delayed
operation. (Refer to function settings
For the heater, observe the cautions listed in
Lossnay
OA
Power Supply
for heater

When switching fan speed externally

7
(when a sensor or other equipment is connected)
Using a field supply sensor, etc., make connection by inserting the
optional remote display adaptor (PAC-SA88HA-E) in the connector
CN17 (Red) as shown by the figure.
Lossnay will operate the fan speed following the table below,
regardless of the remote controller setting.
CN17 (Red)
Fan speed
1-2 (Brown-Red)
4
1-3 (Brown-Orange)
3
1-4 (Brown-Yellow)
2
1-5 (Brown-Green)
1
n Example "Fan speed 4"
Remote display adaptor
Field supply sensor, etc.
(Optional) PAC-SA88HA-E
SW1
Orange 3
Not used. Insulate completely.
Max wiring length 10 m
Use this in such a way that it ventilates at low fan speed normally,
and when the external sensor detects contamination of indoor air,
it changes to high fan speed operation.
)
7
8
9
X15
10
No. 57
)
4
.
2 m or more
SA
TM3
7
8
Relay
9
X15
10
Power Supply
Max 240 VAC, 1 A
24 VDC, 1 A
for relay
Min
220 VAC, 100 mA
5 VDC, 100 mA
Lossnay
control board
Brown 1
CN17
Red 2
Yellow 4
Fan speed
Green 5
selection
Eng-11